2-11. Electrical Service Guide

Input Voltage

200

230

Input Amperes At Rated Output

30

26

Max Recommended Standard Fuse Or Circuit Breaker Rating In Amperes

Circuit Breaker

1

, Time-Delay

2

35

30

Normal Operating

3

45

40

Min Input Conductor Size In AWG/Kcmil

10

10

Max Recommended Input Conductor Length In Feet (Meters)

97

(29)

128

(39)

Min Grounding Conductor Size In AWG/Kcmil

10

10

Reference: 1999 National Electrical Code (NEC)

1 Choose a circuit breaker with time-current curves comparable to a Time Delay Fuse.

2 “Time-Delay” fuses are UL class “RK5” .
3 “Normal Operating” (general purpose – no intentional delay) fuses are UL class “K5” (up to and including 60 amp), and UL class “H” ( 65 amp and

above).

Y

Caution: Failure to follow these fuse and circuit breaker recommendations could create an electric shock or fire hazard.

2-12. Selecting A Location And Connecting Input Power

1

Rating Label

Supply correct input power.

2

Plug

3

Receptacle

Connect plug to receptacle.

4

Input And Grounding
Conductors

Connect directly to line disconnect
device if hard wiring is required.

5

Line Disconnect Device

See Section 2-11.

Y

Special installation may be
required where gasoline or
volatile liquids are present –
see NEC Article 511 or CEC
Section 20.

Ref. 801 568 / Ref. 800 797-C

L1

L2

230 VAC, 1

18 in (457 mm) of
space for airflow

L1
L2

1

Y

Always connect grounding
conductor first.

= GND/PE

Y

Do not move or operate unit
where it could tip.

4

2

3

1

5