Radiance Natural Vent Gas Heater

20004409

Clearance Requirements

Minimum Clearances to

Combustible Materials

Measure side clearances as shown in Figures 2
through 5 from the outer edge of the cast iron stove
top. Measure rear clearances from the rear sheet metal
shroud.

The Radiance heater is approved for installation into
an alcove constructed of combustible materials to the
dimensions and clearances shown on this page.

The same clearances apply in a standard parallel
installation.

Fig. 4 Minimum ceiling clearance: minimum alcove height.

42"

(1070mm)

4"

(100mm)

6"

(150mm)

6"

(150mm)

Alcove Minimum Dimensions

Fig. 5 The Radiance Natural Vent Stove is approved for
installation into alcoves built of combustible materials.

Hearth Requirements

The Radiance Heater must be installed on rigid floor-
ing. When the heater is installed directly on any
combustible surface other than wood flooring, a metal
or wood panel extending the full width and depth of the
unit must be used as the hearth. There are no other
hearth requirements.

WARNING:

• Always maintain required

clearances (air spaces) to nearby combustibles
to prevent fire hazard. Do not fill air spaces with
insulation. All venting components must
maintain a 1" (25mm) clearance to combustible
materials. Maintain a 6” (150mm) clearance
when using single wall pipe.

• The gas appliance and vent system must be

vented directly to the outside of the building
and never be attached to a chimney serving a
separate solid fuel or gas-burning appliance.

• Refer to the manufacturer's instructions

included with the venting system for complete
installation procedures.

46"

(1168mm)

74"

(1880mm)

R A D I A N C E

Ceiling Clearances

ST131b

Parallel Installation: Minimum Clearance

and Flue Centerline

ST128b

Fig. 2 Parallel installation, minimum back and side clear-
ances, and flue centerlines.

C

L

C

L

C

D

B

A

Stove Clearance

A: 4” (100mm)
B: 6” (150mm)

Pipe Centerline

C: 21

⁷⁄₈

“ (556mm)

D: 8

¹⁄₂

” (216mm)

Corner Installation: Minimum

Clearance and Flue Centerline

B

B

A

A

Stove Clearance:

A: 6” (150mm)

Pipe Centerline:

B: 18” (460mm)

ST129b

Fig. 3 Corner installation requirements.