SET ROOM THERMOSTAT TO

HIGH STOP POSITION

Check voltage across fan high limit switch

terminals (56).

MODEL: EXT

FUNCTION: Air Delivery

PROBLEM: Fan(s) do not operate.

Before starting any procedures listed below, check room thermostat and circuit breaker settings.

Make sure there is appropriate line voltage between F1/F3 terminal block positions in the heater.

The room temperature cannot exceed 85 degrees when performing the following test procedures.

NOTE: For cross reference to number coded components, refer to the Exploded View Diagram.

Check room thermostat (23) for

possible miscalibration.

Check voltage across F2 & F3

terminal block positions (24).

Fan(s) Do Not

Operate

Fan(s) Operate

Voltage

Present

Remove the purple wires from

the room temperature control

thermostat (23) and jumper

them together.

No Voltage Present

Replace

thermostat (23).

Fans Run

Check unit wiring.

Fans Do

Not Run

Fix Unit Wiring.

Replace Circuit

Board (29).

Incorrect

Correct

Replace fan limit

switch (56).

Remove fan assembly

(47) and check voltage

to fan motor(s) (53).

Voltage Present

No Voltage

Present

Check units

internal wiring.

Check fan impeller for

debris that could cause

jamming. Replace if

necessary.

No Voltage

Present

Voltage

Present