Steffes 5140 Simplified Installation Guide User Manual

Quick reference installation guide, Comfort plus hydronic, Placement and clearances set-up

Advertising
background image

1

2

PLACEMENT AND CLEARANCES

SET-UP

Minimum Clearance Requirements

A Back and Right Side = 3 inches from

combustibles

B Front = 36 inches

C Top = 6 inches from combustibles

D Bottom = 1 inch from combustibles

E Left Side = 36 inches

Quick Reference Installation Guide

3

BRICK LOADING

1. Place system in desired location.

2. Adjust leveling legs.

3. Remove painted front panel of brick

storage cabinet.

4. Position element wiring harnesses

to avoid damage during brick

loading.

5. Position brick core temperature

sensor(s) to avoid damage during

brick loading.

6. Remove galvanized front panel.

7. Starting at bottom, lift and drape

insulation blankets over top of

system.

8. Remove front air channel by pulling

out at top.

9. Remove heating elements from

inside brick core cavity.

• DO NOT extend leveling legs

more than one inch.

• DO use and follow generally

accepted safety practices when

handling insulation material.

• Equipment MUST be installed by

a qualified technician in accor-

dance with all applicable local,

state and national codes and

regulations.

• Reference Owner’s and Installer’s

Manual for complete safety,

installation, and operation

instructions.

Starting at the back of the brick core cavity,

load bricks one row at a time using left side,

right side, center pattern. Place bricks with

grooved side facing up, notch facing forward,

and ridges on left and right.

• Remove loose

debris from brick.

• Brick rows MUST line

up front to back

and side to side.

• Use half bricks in proper rows and in

correct positions. Back half of brick

MUST be installed in back rows. Front

half (notched brick piece) MUST be

installed in front rows.

If area available to install Comfort

Plus Hydronic system is less than 100

square feet, consult factory. If install-

ing in area with less than 400 square

feet, ventilation MUST be provided.

Temperature in area should be

maintained at or below 85

o

F.

TOP VIEW

A

B

A

E

D

A

C

FRONT VIEW

M

A
M

M

P

“Manufactured in North America”

COMFORT PLUS

HYDRONIC

Models 5120, 5130, 5140

Fro

nt o

f U

nit

Notch in Brick

HALF BRICK

5120: Load in row 5

5130: Load in row 4 and 8

5140: Load in row 6 and 12

CA

CA

CA

CA

CAUTION

UTION

UTION

UTION

UTION

WARNING

WARNING

WARNING

WARNING

WARNING