PRIMARY LOOP

(* Steffes recommends a Grundfos UP15-42F or equal single

speed 115VAC pump for the primary pump.)

The Comfort Plus Hydronic heating system MUST be plumbed with a primary loop and secondary (zone) loops. The primary loop

needs to consist of a minimum of 10' of 1" pipe and requires its own pump* (circulator). The secondary (zone) loops require

additional pump(s) to operate effectively.

PLUMBING

10

FREEZE PROTECTION: Risk of property damage. Hydronic heating system freeze-ups WILL cause extensive

damage to the entire heating system and/or property. It is the responsibility of the installer to provide protec-

tion against freezing.

PIPING SUPPORT: Risk of equipment damage or personal injury. DO NOT use the exchanger as support for

piping. Support of primary loop and associated plumbing must be installed to ensure proper operation of the

system and to keep pressure off the inlet and outlet piping.

NOTE: The primary loop pump MUST be con-

trolled by the furnace through the red

and white wires. When this pump is

running, water must be allowed to flow

through the heat exchanger.

STATIC PRESSURE

(Feet Water Column)

Based on 80 degree entry

water temperature with

a 50% glycol mix.

.1 ft @ 2 GPM

.2 ft @ 4 GPM

.4 ft @ 6 GPM

.7 ft @ 8 GPM

1.1 ft @ 10 GPM

PRESSURE DROP THROUGH

HEAT EXCHANGER

Expansion

Tank

Air Separator

Primary Loop Pump

Control Wiring

(White & Red)

Junction Box

(Factory Supplied)

*Primary

Loop

Pump

Air Vent

Piping MUST

Be Supported

Pressure

Relief Valve

(Factory Supplied)

Optional

Temperature and

Pressure Relief Valve

(Consult Local Code)

Zone

Connection

Area

Inlet

Outlet

See Note

SINGLE TEMPERATURE ZONES

White

Red

White

Red

Primary

Loop Pump

Comfort Plus

Hydronic

Exchanger

This Valve Must
Be Open During

Normal Operation

WARNING

WARNING

WARNING

WARNING

WARNING

Secondary Loop

Primary Loop

Capacity 1.2 Gallons

Maximum Flow

10 GPM

Tubing Material

Copper

Maximum Outlet

Water Set Temperature

180°F

HEAT EXCHANGER SPECIFICATION