12

BATTERY CHARGE PARAMETERS WEB PAGE

¾

CAUTION: Refer to charge controller operators manual for further detail regarding charge control operation. Set battery charge

parameters to values specified by the battery manufacturer.






























Acceptance charge voltage setpoint.
Range 10.0 to 80.0V.

Float charge voltage setpoint.
Range 10.0 to 80.0V.

Equalize charge voltage setpoint.
Range 10.0 to 80.0V.

Equalize time setpoint.
Range 0.5 to 10.0 hours.

Days between automatic Equalize. Range is 10 to
400 days. Fully MANUAL equalization is selected
by entering a setting of 0 days.

Charge voltage temperature compensation factor.
Range is -0.00 to -8.00mV/

°C/cell.

Sets Float Transition Current. Range 0.1 to 10.0A
per 100 Amp-Hours of battery capacity. A setting of
0.0A disables function such that full charge is
based on Acceptance charge time only.

Sets Acceptance charge time.
Range 0.0 to 10.0 hours.