Ucm setup parameters – Blue Sky UCM User Manual

Page 20

Advertising
background image

Blue Sky Energy – Universal Communication Module

19

3) Force Single Coil (0x05)

Query Packet:

Slave address | Function code 0x05 | MSB coil address | LSB coil address |MSB force data, don’t care |

LSB force data, don’t care | LSB CRC | MSB CRC

Response Packet:

Slave address | Function code 0x05 | MSB coil address | LSB coil address |MSB force data, don’t care |

LSB force data, don’t care | LSB CRC | MSB CRC


FORCE COILS

PDU ADDRESS

LOGICAL COIL #

DESCRIPTION

0x0013 20

Start

Equalize

0x0014 21

Stop

Equalize

0x0015

22

Clear Max. Battery Volts Detected

0x0016

23

Clear Min. Battery Volts Detected

0x0017

24

Clear Total Charge Amp-Hours

0x0018

25

Clear Lifetime Battery Discharge Amp-Hours

0x0019

26

Set Charge Efficiency to Auto Mode

0x001A

27

Set Charge Efficiency to Fixed Mode

0x001B

28

Set Aux. Out Mode to Volts

0x001C

29

Set Aux. Out Mode to Amp-Hours

0x001D

30

Restore Charge Controller Defaults

TABLE 6


UCM SETUP PARAMETERS

¾

The UCM has various setup parameters all of which are preconfigured at the factory. All setting are stored either in nonvolatile

memory, DIP switches or jumpers such that all settings are retained following a loss of power.

As Shipped Factory Default Settings

Basic TCP/IP Communication

FTP File Transfer

• IPv4 IP Address ......................................... 192.168.1.235

• Server address ......................................................... ―blank―

• Subnet Mask .............................................. 255.255.255.0

• User Name ............................................................... ―blank―

• Gateway IP Address ................................. 192.168.1.1

• Password ................................................................... ―blank―

• IP-A (force use of comm defaults) ............ off

• Hours Between Uploads .......................................... Disabled

Datalogging UCM

logon

• Hours in Log Period ................................... Disabled

• Password................................................................... admin

MODBUS
• Address / Unit Identifier ............................. 1 (AD0 ― AD7 all off)

• RS-485 Duplex Mode ............................................... Half Duplex

• RS485 DataBits/Parity/StopBits ............... 8/Even/1 (Baud1/Parity off) • RS-495 Baud rate ..................................................... 19.2K (baud0 off)

Misc.
• Location Name Reminder ......................... MY SOLAR SYSTEM

Restoring As Shipped Factory Default Settings

1. Remove UCM power

5. Set all 12 DIP’s shown in Figure 4 to OFF

2. Set DIP’s AD0 ― AD7 shown in Figure 4 to all ON

6. Install two jumper plugs

A-to-A’ and B-to-B’

shown in Figure 4

3. Restore UCM power for 10 seconds, confirm power LED blinking

7. UCM is now restored to As Shipped Factory Default Settings

4. Remove UCM power

)

Advertising