Blue Sky IPN Pro User Manual

Page 7

Advertising
background image

Installation and Operation Manual

6

ADVANCED DISPLAY Menu



From Top menu




















































To Setup menus
if selected.









FIGURE 3

LAST FULL CHARGE
10 DAYS AGO

Days since last full charge or equalize. The equalize day counter resets upon
commencing equalize.

Day counter accuracy is +1 / -0 days as day counter transitions occur following
each 24 hour period from when battery power was applied. Consider applying
battery power late in the evening to improve counter accuracy. Maximum range is
255 days which is also shown if days are unknown.

LAST EQUALIZE
22 DAYS AGO

MAX BAT VOLTS
15.4V CLR

Captures minimum and maximum battery voltage since last cleared.

MIN BAT VOLTS
11.9V CLR

TOTAL CHG AMP-HR
+1980AH CLR

Captures total output amp-hours of all charge controllers on the IPN network since
last cleared.

LIFETIME BAT AH
-9876543AH CLR

Serves as battery “odometer” capturing total discharge amp-hours since last
cleared. Value saved to non-volatile memory once per day.

BAT TEMPERATURE
25C 77F

Shows present battery temperature if optional sensor installed on charge
controller.

ENTER SETUP
MENUS SEL

VIEW CHARGE UNIT
STATUS SEL

Selects status display of controllers on IPN network.

0 +25C OUT 12.3A
IN 17.5V 12.0A

7 +29C OUT 14.5A
IN 18.5V 15.0A

Controller address #0 – 7. NEXT scrolls through each
controller status screen. BACK returns to Advanced Display
menu.

* Screen will be blank except for address if controller not
communicating on network.

Output current *

PV Input current *

PV Input voltage *

Internal temperature *

Advertising