Installation and Operation Manual

8

BATTERY CHARGE PARAMETERS Menu

‘

From Setup menu













































FIGURE 5

SET ACCEPT CHG
14.4V SEL

Sets Acceptance charge voltage setpoint.
Range 10.0 to 80.0V.

SET FLOAT CHG
13.4V SEL

Sets Float charge voltage setpoint.
Range 10.0 to 80.0V.

SET ACCEPT TIME
2.0HRS SEL

SET FLOAT CURENT
1.5A/100AH SEL

Sets Float Transition Current. Range 0.1 to 10.0A per 100 AH. A setting of 0 (zero)
disables function such that full charge is based on acceptance charge time only.
See charge controller operators manual.

SET EQUALIZ CHG
15.2V SEL

Sets Equalize voltage setpoint.
Range 10.0 to 80.0V.

SET EQUALIZ TIME
2.0HRS SEL

Sets Equalize time.
Range 0.5 to 10 hours.

SET AUTO EQUALIZ
30DAYS SEL

Sets days between automatic Equalize. Range is 10 to 400 days. Fully MANUAL
equalization is selected by a setting of less than 10 days.

SET T-COMP SLOPE
-5.00mV/C/C SEL

Sets charge voltage temperature compensation factor. Range is -0.00 to -
8.00mV/

°C/cell.

Sets Acceptance charge time.
Range 0.0 to 10.0 hours.