4 | compressor assembly – GEA Bock HG7 R134a User Manual

Page 12

Advertising
background image

12

D
GB
F
E

96182-01.2015-DGbFEI

4| Compressor assembly

Fig. 12

Fig. 13

Valve spindle seal

Release

Tighten

Pipe connection

Pipe connection

4.7 Operating mode of the lockable service connections

Fig. 14

Opening the shut-off valve:
Spindle: turn to the left (counter-clockwise) as far as it will go.
—> Shut-off valve completely opened / service connection closed.
The connection which cannot be shut off is intended for safety devices.

Fig. 15

Opening the service connection
Spindle: Turn ½ - 1 turn to the right clockwise.
—> Service connection opened / shut-off valve opened.
The connection which cannot be shut off is intended for safety devices.

Service connec-
tion closed

Connection
blocked

Spindle

Connection cannot be
shut off

Connection cannot be
shut off

Service connec-
tion opened

Spindle

Connection
open

Compressor

Compressor

Before opening or closing the shut-off valve, release the valve spindle seal by approx. ¼ of a turn

counter-clockwise.

After activating the shut-off valve, re-tighten the adjustable valve spindle seal clockwise.

4.6 Operating the shut-off valves