16

D
GB
F
E

96182-01.2015-DGbFEI

400 V

Direktstart YY

Teilwicklungsstart Y/YY

1V1

1W1

1U1

2W1

2V1

2U1

L3

L2

L1

L3

L2

L1

L3

L2

L1

1V1

1W1

1U1

2W1

2V1

2U1

Direct start YYY

Part winding start

Δ/YYY

ATTENTION! Failure to do this results in opposed rotary fields and results in

damage to the motor. After the motor starts up via partial winding
1, partial winding 2 must be switched on after a maximum delay of
one second . Failure to comply can adversely affect the service life
of the motor.

The motor is wired for direct start (YYY) at the factory. For part winding start

Δ/YYY the bridges must

be removed and the motor feed line connected according to the circuit diagram:

INFO!

When testing coils with resistance tester, please note that partial

winding 1 and partial winding 2 are wired internally in HGX7.

5.3 Standard motor, design for direct or part winding start

Designation on the name plate

Sticker on the terminal box

/YYY

Compressors with this marking are suitable for direct or partial winding start. The motor winding is
subdivided into two parts: Partial winding 1 = 60% and part winding 2 = 40%. This winding division
reduces the start-up current needed for a part winding start to approx. 65% of that for a direct start.

INFO!

A mechanical unloaded start with bypass solenoid valve is

not required.