3| Areas of application

The compressors are filled at the factory with the following oil type:

FUCHS Reniso Triton SE 55
Compressors with ester oil charge (FUCHS Reniso Triton SE 55) are marked with an X in the type
designation (e.g. HG

X7/2110-4 R134a).

3.1 Refrigerants
• HFKW / HFC: R134a

3.2 Oil charge

INFO!

For refilling, we recommend the above oil types.

Alternatives: see lubricants table, Chapter 7.5.

ATTENTION! Compressor operation is possible within the operating limits

shown in the diagrams. Please note the significance
of the shaded areas. Thresholds should not be selected as design
or continuous operation points.

- Permissible ambient temperature (-20°C) - (+60°C)

- Max. permissible discharge end temperature 140 °C

- Max. permissible switching frequency 12x /h.

- A minimum running time of 3 min. steady-state condition

(continuous operation) must be achieved.

For operation with supplementary cooling:

- Use only oils with high thermal stability.

- Avoid continuous operation near the limits.

For operation with capacity regulator:

- The suction gas superheat temperature may need to be reduced

or set individually when operating near to the threshold.

For operation with frequency converter:

-

The maximum current and power consumption must not be

exceeded. In the case of operation above the mains frequency,
the application limit can therefore be limited.

During operation in the vacuum range, there is a danger of air

entering on the suction side. This can cause chemical reactions,

pressure rise in the condenser and an excessive compressed-gas

temperature. Avoid absolutely any entry of air:

3.3 Limits of application

The oil level must be in the
visible part of the sight
glass; damage to the com-
pressor is possible if over-
filled or underfilled!

ATTENTION!

max.

min.

2,3 Ltr.

oil level

Fig. 3

~

~