16

D
GB
F
E

96179-01.2015-DGbFEI

5| Electrical connection

400 V

Direktstart YY

Teilwicklungsstart Y/YY

1V1

1W1

1U1

2W1

2V1

2U1

L3

L2

L1

L3

L2

L1

L3

L2

L1

1V1

1W1

1U1

2W1

2V1

2U1

Direct start YY

Part winding start Y/YY

ATTENTION! Failure to do this results in opposed rotary fields and results in

damage to the motor. After the motor starts up via partial winding
1, partial winding 2 must be switched on after a maximum delay of
one second. Failure to comply can adversely affect the service life
of the motor.

The motor is wired for direct start (YY) at the factory. For part winding start Y / YY, the bridges must be
removed and the motor feed line connected according to the circuit diagram: