5| Electrical connection

The compressor and the trigger unit MP10 are operational when the H3 LED (green) lights.

5.8 Function test of the trigger unit MP 10

Pos

Procedure

LED H1 LED H2 LED H3

red

red

green

1 Interrupt power supply (L1 or S1)

OFF

OFF

OFF

Release the motor temperature sensor connection (1 or 2)

Release the hot gas temperature sensor (if installed) (3 or 4)

2 Restore the power supply (L1 or S1)

ON

Function check of motor temperature sensor: operational

ON

Function check of hot gas temperature sensor: operational

ON

3

Interrupt power supply again (L1 or S1)

OFF

OFF

OFF

Reconnect terminals 1 or 2 and/or 3 or 4

4

Restore the power supply (L1 or S1):

OFF

OFF

ON

MP 10 is operational again

Before start-up, troubleshooting or making changes to the control power circuit, check the functionality
of the trigger unit: