5| Electrical connection

ATTENTION!
Terminals 1 - 6 on the trigger
unit MP 10 and terminals PTC
1 and PTC 2 on the compres-
sor terminal board must not
come into contact with mains
voltage. This would destroy the
trigger unit and PTC sensors.
The supply voltage at L1-N
(+/- for DC 24 V version) must
be identical to the voltage at
terminals 11, 12, 14 and 43.

5.6 Electronic trigger unit MP 10
The compressor motor is fitted with cold conductor temperature sensors (PTC) connected to the
electronic trigger unit MP 10 in the terminal box. Readiness to operate is signalled by the H3 LED
(green) after the power supply is applied. In the case of excess temperature in the motor winding, the
unit switches off the compressor and the H1 LED lights red.
The hot gas side of the compressor can also be protected against overtemperature using a thermal
protection thermostat (accessory). The H2 LED (red) is provided for the protection function.
The unit trips when an overload or inadmissible operating conditions occur. Find and remedy
the cause.

5.7 Connection of the trigger unit MP10

INFO!

Connect the trigger unit MP10 in accordance with the circuit dia-
gram. Protect the trigger unit with a delayed-action fuse (F) of max.
4 A. In order to guarantee the protection function, install the trigger
unit as the first element in the control power circuit.

Temperature monitoring connections:

Motor winding:

Terminals 1 - 2

Thermal protection thermostat:

Terminals 3 - 4

Restart prevention:

Terminals 5 - 6

INFO!

The unit has a restart prevention device. After you have rectified the
fault, either interrupt the mains voltage. This unlocks the restart pre-
vention device and the LEDs H1 and H2 go out.