4| Compressor assembly

4.3 Pipe connections

The

pipe connections have stepped internal diameters so that pipes with

standard millimetre and inch dimensions can be used.

The connection diameters of the shut-off valves are designed for maximum

compressor output.

The required pipe cross-section must be matched

to the capacity. The same applies for non-return valves.

The required tightening torque for the flange connection is 60 Nm.

Fig. 14: stepped
internal diameters

4.2 Maximum permissible inclination

Fig. 13

A

A

a

a

A

A

a

a

A

max. 30°,
max. 2 minutes

a

max. 15°,
continuous
operation

ATTENTION Risk of compressor damage.

Poor lubrication can damage the compressor.
Respect the stated values.

ATTENTION Risk of damages.

Overheating can damage the valve.
Remove the pipe supports from the valve for soldering.
Only solder using inert gas to inhibit oxidation products (scale).

4.4 Pipes

Pipes and system components must be clean and dry inside and free of scale, swarf and layers of

rust and phosphate. Only use air-tight parts.

Lay pipes correctly. Suitable vibration compensators must be provided to prevent pipes being

cracked and broken by severe vibrations.

Ensure a proper oil return.
Keep pressure losses to an absolute minimum.