Chateau™

20011956

Fig. 13 Termination clearances.

Quick Reference for Fresh Air Restrictor Plate / Flue Baffle

Application

Item

DVT38N

DVT38P

DVT44N

DVT44P

SK8DVSK

Flue Restrictor Plate

3”

None

None

4¹⁄₂”

Fresh Air Restrictor Plate

None

None

None

#1

Vertical Less than 12’ Flue Restrictor Plate

None

None

None

None

Fresh Air Restrictor Plate

None

None

None

None

Vertical 12’ to 20’

Flue Restrictor Plate

4¹⁄₂”

4¹⁄₂”

4¹⁄₂”

4¹⁄₂”

Fresh Air Restrictor Plate

#3

#3

#3

#3

Vertical 20’ to 30’

Flue Restrictor Plate

4¹⁄₂”

4¹⁄₂”

4¹⁄₂”

4¹⁄₂”

Fresh Air Restrictor Plate

#2

#2

#2

#2

Vertical 30’ to 40’

Flue Restrictor Plate

4¹⁄₂”

4¹⁄₂”

4¹⁄₂” or 6³⁄₄”

4¹⁄₂” or 6³⁄₄”

Fresh Air Restrictor Plate

#1

#1

#1

#1

Outside Corner

Inside Corner

Termination Clearances

Termination clearances for buildings with combustible and noncombustible exteriors.

G =

Combustible

6" (152 mm)

Noncombustible

2" (51 mm)

F =

Combustible

6" (152 mm)

Noncombustible

2" (51 mm)

G

Balcony -

with no side wall

M =
Combustible &
Noncombustible
12" (305 mm)

M

Balcony -

with perpendicular side wall

M = 24" (610 mm)
P = 20” (508 mm)

M

F

Alcove Applications*

C

D

C

E

V

V

Combustible &

Noncombustible

V

V

V

E

= Min. 6” (152 mm) for

non-vinyl sidewalls
Min. 12” (305 mm) for
vinyl sidewalls

O

= 8’ (2.4 m) Min.

O

P

584-15

No.

of Caps

D

Min.

C

Max.

1

3’ (914 mm) 2 x D

Actual

2

6’ (1.8 m)

1 x D

Actual

3

9’ (2.7 m)

2/3 x D

Actual

4

12’ (3.7 m)

1/2 x D

Actual

D

Min.

= # of Termination caps x 3

C

Max.

= (2 / # termination caps) x D

Actual

*NOTE: Termination in an alcove space (spaces open only on one side and with an overhang) is permitted with the dimensions
specified for vinyl or non-vinyl siding and soffits. 1. There must be a 3’ (914 mm) minimum between termination caps. 2. All
mechanical air intakes within 10’ (1 m) of a termination cap must be a minimum of 3’ (914 mm) below the termination cap. 3. All
gravity air intakes within 3’ (914 mm) of a termination cap must be a minimum of 1’ (305 mm) below the termination cap.

NOTE: Refer to Page 22, Figure 35 for instructions to fabricate 3” and 4¹⁄₂” flue restrictor plates.