5.3 Module/Unit Connections

KV

-300

KV-10/80

5

Chapter 5 KV-300 Hardware

1-180

5.3.4

Mounting to the DIN Rail

To mount the KV-300 Series to the DIN rail, follow the procedure below.

1. Engage the KV-300 with the upper edge of the DIN rail. Pivot the lower portion of

the KV-300 against the DIN rail until a click is heard.

2. Check that the unit is secured to the DIN rail with the clip as shown in A below.

Mount I/O terminal modules to the DIN rail in the same manner.

3. To remove a module, pull out the clip until it appears as shown in B above and

detach the module from the DIN rail.

4. To remount a removed module, push the clip (B) in the direction of the arrow until

it appears as A above, then engage the module with the rail.

B

A

Connection order

When connecting modules, place the AC power supply module or DC power distri-
bution module (KV-U4/U5) at the leftmost position and connect the KV-300 CPU
immediately to the right of the KV-U4/U5. Connect the other modules to the CPU in
any order desired.*

Note: Connect the right-end plate only to the right-end module.

*

I/O addressing may vary according to connection order.

CPU

U5

U4

End plate