Appendix B Specifications and Dimensions

KV-300 Series

Appendicies

Appendices

1-396

For KV-10/80 users

Output specifications

Relay service life: Mechanical: 20 million operations min.

Electrical: 100 thousand operations min. (20 times/min)

I/O circuit configuration

Input circuit (relays 0000 to 0005)

*4.3 kΩ used only for terminals connected to relays other than 0000 through
0005.

Input from both NPN [(+) connected to COM] and PNP [(–) connected to COM]
type transistors are applicable.

Output circuit (relay contact)

Applicable only to the KV-40R, KV-24R, KV-16R, KV-10R, and KV-8ER.

A separate power supply is required for the load.

Type of output

Relay

BJT

MOS-FET

Rated load

250 VAC/

30 VDC 0.3 A

30 VDC 0.25 A

Max. voltage at OFF

30 VDC

30 VDC

Leak current at OFF

100 µA max.

5 µA max.

Residual voltage at

1V

ON

Resistance at ON

50 mΩ max.

1Ω max.

OFF

ON 10 ms max.

50 µs max.

350 µs max.

(terminals 500 on

(terminals 500 and 501)

KV-80T(W): 3 µs max.)

2 ms max.
(other terminals)

ON

OFF 10 ms max.

450 µs max.

150 µs max.

(terminals 500 on
KV-80T(W): 20 µs)

Photocoupler insulation

IN

COM

*4.3k

+

+

Internal circuit

510 Ω

24 VDC

3k Ω

Power supply for operating
relay 24-VDC power is
internally supplied.

COM

+

+

Internal circuit

L

~

OUT

Switching
time