5.3 Module/Unit Connections

KV

-300

KV-10/80

1

5

Chapter 5 KV-300 Hardware

1-187

5.3.8

I/O Terminal Modules: Communication Cables and
Power Distribution

Use only the specified cable when connecting to terminal modules. Use of any
other cable may cause communication errors.

Transmission distance by cable type

AWG18 twisted pair or

VCTF

0.75 mm

2

120 m (Total length)

AWG16 twisted pair or

VCTF

1.25 mm

2

120 m (Total length)

RG-58 coaxial or 3D-2V

200 m (Total length)

Connection patterns

Connections and branching between remote I/O terminal modules can be arranged
as desired; however, the total length of the wiring must not exceed that specified
above.

➮ Refer to page 1-188 for power distribution lines.

CAUTION

KV

-R1A

R16/R8

R16/R8

R16/R8

R16/R8

R16/R8

Note: When connecting communication cables, connect S+ to S+ and S- to S-.

R16/R8: I/O terminal module
KV-R1A: I/O Distribution module

1

2

3

4

5

[Total length of wiring = (1) + (2) + (3) + (4) + (5)]

R16/R8

R16/R8

R16/R8

R16/R8

R16/R8

R16/R8

R16/R8

R16/R8

R16/R8

KV

-R1A

1

2

3

4

5

6

7

8

9

[Total length of wiring = (1) + (2)+ (3) + (4) + (5) + (6) + (7) + (8) + (9)]

S+
S–

S+
S–

S+
S–

Correct

Incorrect

* You can use either wire of the twisted pair

for S+ or S-. Also, you can use either the
core cable or the braided cable.
However, do not change the combination in
the system.

Use only the specified cable when connecting to terminal modules. Use of
any other cable may cause communication errors.

The cable can be selected from the three types shown above.
However, use only one type in a system. Mixing more than one type may
cause a malfunction.

CAUTION