Vi. plc input/output configuration table – Kistler-Morse KM SVS2000 User Manual

Page 11

Advertising
background image

OUTPUT WORD

WORD

16

15

14

13

12

11

10

9

8

7

6

5

4

3

2

1

1

Tare MSW

2

Tare LSW

CH4*

CH3*

CH2*

CH1

3

Read/Write

WR

RD

4

Variable ID

5

Variable Write MSW

* Channels 2-4 only available

on Weigh II

6

Variable Write LSW

INPUT WORD

WORD

16

15

14

13

12

11

10

9

8

7

6

5

4

3

2

1

1

Gross MSW

2

Gross LSW

3

Net MSW

4

Net LSW

5

Status MSW

6

Status LSW

Not Used

Not Used

Not Used

Not Used

FORMAT BITS

Gr

oss Units Negative

Gr

oss/Net Unit

Err

or

ADC Err

or

Comm Err

or

A

vg or

C

al

ib

ra

tio

n

Er

ro

r

Move Mor

e

Material

Not Used

Net Units Negative

7

Variable Read MSW

8

Variable Read LSW

VI. PLC INPUT/OUTPUT CONFIGURATION TABLE

FORMAT BITS

12

11

10

9

XXXXXX

0

0

0

0

XXXXXX00

0

0

0

1

XXXXXX00

0

0

1

0

XXXXX.X

0

1

0

0

XXXX.XX

0

1

0

1

XXX.XXX

0

1

1

0

* Channels 2-4 only available

on Weigh II

At this point weight data and status should be received by the PLC. The PLC should be able to set the required tare
command bit in order to force the SVS2000 to tare and read/write a supported variable. Currently there are only two (2)
supported variables that can be read/written.

Read/write is optional and not required for gross/net values.

• TO READ A VARIABLE:

a. In the Output Word, set Read/Write bit (line 3) to

000000000000001

b. In the Output Word, set the Variable ID (line 4) to

000000000000001 for Setpoint 1 or 0000000000000010

for Setpoint 2. Subsequently, the value will be returned in

the Input Word, Variable Read (line 8).

• TO WRITE A VARIABLE:

a. In the Output Word, set Read/Write bit (line 3) to

000000000000010

b. In the Output Word, set the Variable ID (line 4) to 000000000000001 for Setpoint 1 or 0000000000000010

for Setpoint 2.

c. Add the new input values, in binary, to the Output Word, Variable Write (line 6 or 5 and 6). What is

written in line 6 or 5 and 6 will show up on the Input Word in lines 8 or 7 and 8. Invalid values will be

ignored.

7

www.kistlermorse.com

97-1501-12 Rev. B

Advertising