III. SETTING UP THE OUTPUT CARD FOR THE SVS2000

A network consists of two or more nodes interconnected that each have a unique address. For each installation,
unique parameters must be configured in the output module prior to connecting the module to the network so a
conflict or error does not occur.

1. Route the customer supplied network cabling through one of the holes in the bottom of the SVS2000,

connecting it to the top PCB of the output module. Refer to Section VIII, for wiring diagrams.

2. The front panel can now be re-installed and power applied.

3. To change the output interface parameters that require editing:

a. Press the ‘GROSS’ key to access the Run Mode.

b. Press the ‘5’ key and ‘3’ key followed by the ‘ENTER’ key to access the menu tree. The display

reads: 53 PLC MENU

c. Press the ‘ENTER’ key to access the PLC Menu. The display reads: A-B RIO MENU

FOR DEVICENET

The DeviceNet Module factor default configuration is Node 5 and 250k baud rate.

d. Press the ‘DOWN’ arrow key until the DeviceNet menu appears. Press the ‘ENTER’ key.

The display reads: DeviceNet MENU

e. Press the ‘UP’ arrow key until the DeviceNet ID appears. The display reads: DeviceNet ID

f. Press the ‘ENTER’ key to view the current Node Address and to allow editing. The display

reads: 5 ID

g. Edit the Node Address at this time using the numeric keys. The range can be from 1 to 63. Press

the ‘ENTER’ key after entering the Node Address. The display reads: DeviceNet ID

h. Press the ‘UP’ arrow key to access the baud rate. The display reads: BAUD RATE

i. Press the ‘ENTER’ key to access the Baud Rate Menu. (Asterisk indicates the current selection)

The display reads: BAUD RATE: *250K. Press the ‘UP’ arrow key to select the desired baud rate.

Baud Rate

500K

250K

125K

IP Address

Subnet Mask

Default Gateway

DeviceNet ID

53 PLC Menu

A-B RIO

Operation Mode

Profibus Node

Rack Address

Rack Size

Last Rack

Baud Rate

Starting

Qualifier

Default RID

Module

DeviceNet

EtherNet

Profibus

2