Kistler-Morse KM SVS2000 User Manual

Page 8

Advertising
background image

FOR PROFIBUS DP

The Profibus Module is shipped from the factory configured for node 4. The node address is changeable via the
DIP switches on the Profibus PCB Module. Switches one (1) through eight (8) configure the node address where
switch one (1) is the LSB and switch eight (8) is the MSB. When the switch is in the on position the value is a
one (1), and when the switch is off the value is zero (0). The Profibus Module will auto baud to the network baud
during power-up. The table below provides examples.

SW8

SW7

SW6

SW5

SW4

SW3

SW2

SW1

NODE ADDRESS

0

0

0

0

0

0

0

0

0

0

0

0

0

0

0

0

1

1

0

0

0

0

0

0

1

0

2

0

0

0

0

0

1

0

0

3

0

0

0

0

1

0

0

0

4

1

1

1

1

1

1

0

1

125

1

1

1

1

1

1

1

0

126 (Reserved for SSA)

1

1

1

1

1

1

1

1

INVALID

4. Configure the PLC to match the selections made to the SVS2000.

If you started this procedure with the SVS2000™ Field Firmware Upgrade then you will need to go back to those
instructions now in order to restore the calibration/set up parameters.

IV. SETTING UP THE ETHERNET MODULE (ETHERNET/IP ONLY)

Once the signal processor is wired into the EtherNet/IPTM network with a valid IP address and powered up,
it should be possible for the device to be added to the configuration of the PLC. A copy of the EDS file was
included with the product and is located on the CD. See the screen shot of a typical installation using
RSLogix 5000:

There are four (4) 32 bit Input Connection Parameters

• one double word input of Gross Weight

• one double word input of Net Weight

• one double word input of Status

• one double word input of variable read data.

There are three (3) 32 bit Output Connection Parameters

• one double word output of Tare Command

• one double of read write data

• one double word of variable read data.

4

www.kistlermorse.com

97-1501-12 Rev. B

Advertising