Kistler-Morse KM Load Stand II User Manual

Page 26

Advertising
background image

97-1100-01 Rev. H

22

www.kistlermorse.com

SYMPTOM

POSSIBLE CAUSE

SOLUTION

(Continued from
previous page)

Small Amplitude
Changes or Erratic
Fluctuations in
Display Readings

(Continued from previous page)

Fluctuations can be caused by
damaged Load Stand sensor.

Problem likely to be noticed
shortly after initial installation
or on system that previously
functioned correctly.

7. Identify damaged sensor at Load Stand identified in Step 3, 4, or 5:

a. Remove one sensors’s wires from junction box terminal TB3.

b. Put one DMM lead on sensor’s white wire and other lead on red wire.

Record resistance, and verify it is 7,660 ± 200 ohms. If resistance is

outside this range, sensor is damaged and must be replaced.

c. Put one DMM lead on sensor’s white wire and other lead on black

wire. Record resistance, and verify it is 7,660 ± 200 ohms. If

resistance is outside this range, sensor is damaged and must be

replaced.

d. Verify readings from Steps B and C are within 200 ohms of each

other. If not, sensor is damaged and must be replaced.

e. Repeat Steps A through D for each sensor, until damaged sensor is

located and replaced.

Fluctuations in readings can be
caused by short to ground.

Problem likely to be noticed
shortly after initial installation
or on system that previously
functioned correctly.

Using a Digital Multimeter (DMM) or ohmmeter, check for shorts to ground
as follows:

1. Set meter resistance scale to accommodate maximum measured range.

2. Disconnect junction box wires of suspect vessel from signal processor.

3. With one lead to earth ground and other lead to white wire, check

resistance on disconnected wires:

• If reading is less than infinite (i.e., there is resistance), a short is

indicated; proceed to Step 4 to identify location.

• If no short is indicated, investigate other explanations for problem.

4. Starting with junction box closest to signal processor in daisy chain,

disconnect wires connecting junction box to other junction boxes. With

one lead to earth ground and other lead to white terminal on TB3, check

resistance on wires leading from junction box:

• If the reading is less than infinite (i.e., there is resistance), short is

indicated; proceed to Step 5 to identify location.

• If no short is indicated, proceed to next junction box in daisy chain,

disconnecting wires connecting it to other junction boxes and

checking resistance. Perform for each junction box down chain until

short is located; proceed to Step 5 to identify location.

Note: Sun shield or junction box mounting bolts are good locations for
connecting probe to ground.

5. Disconnect wires for one sensor from above-identified junction box. With

one lead to earth ground and other lead to white wire, check resistance

on disconnected sensor wires:

• If reading is less than infinite (i.e.,there is resistance), short is

indicated. Replace shorted sensor.

• If no short is indicated, disconnect next sensor’s wires from junction

box and check resistances. Repeat for each sensor wired to junction

box until short is located. Replace shorted sensor.

Fluctuations in readings can be
caused by problems with signal
processor.

Problem likely to be noticed
shortly after initial installation
or on system that previously
functioned correctly.

Check signal processor excitation voltage and incoming AC voltage for
accuracy and stability (refer to signal processor manual).

Advertising