3.4 ACS/BMS II Wiring Connections to ProtoNode RER and LER

• When an ACS, BMS OR BMS II is being used, an RS-485-to-RS-232 converter will be

required to connect it to the ProtoNode’s RS485 port (6-pin Phoenix connector).

• Refer to Figures 3-6 and 3-7 to locate the internal RS-232 connector JP12 (BMS) or JP5

(BMS II/ACS) inside the wiring area of the ACS/BMS II.

• If the AERCO RS232-to-RS485 Converter (part no. 124943) is used, the RS-232 side of the

converter contains a connector that plugs directly into header connector JP12 (BMS) or JP5
(BMS II/ACS).

• If a third party converter is used, connect the RS-232 Receive (RxD) and Transmit (TxD)

wire leads to the internal RS-232 connector (JP12 or JP5) as shown in Figures 5 and 6. DO
NOT connect the wire shield on this side of the converter.

NOTE

If a third-party RS232-to-RS485 Converter is used, consult the
manufacturer’s instruction manual for signal polarity.

• On the RS-485 side of the converter (Figure 3-6 and 3-7), connect the wire leads as follows:

o

Connect the TD B (+) terminal to the ProtoNode’s RS485+ Port.

o

Connect the TD A (-) terminal to the ProtoNode’s RS485- Port.

o

Connect the GND terminal to the ProtoNode’s RS485 Frame GND Port.

o

Place the ProtoNode’s termination jumper in the ON position.

FIGURE 3-6: RS-232 Connection to BMS

FIGURE 3-7: RS-232 Connection to ACS/BMS II