Appendix B.4: Water Heater Management System (WHM) and On-
Board Boiler Sequencing Technology (BST) Point Definitions

Appendix B.4: AERCO WHM and BST Point Definitions

Point Name

BAS

Modbus

Data

Address

GF-108,
GF-124,

GF-114

Point

Name

Reg.

Type

Modbus Data

Address

(Hex/Dec.)

Units (Range)

WHM or BST Master

Write Control to WHM/BST

40051

Holding

50

Write “1” to send value to WHM/BST

Read WHM Timeout

40053

Holding

52

0 to

Read WHM Mode

30100

Input

99

0 = OFF, 1 = Slave, 2 = Master

Read WHM Setpoint

30101

Input

100

°F (40 to 200)

Read WHM Setback Setpoint

30102

Input

101

°F (40 to 200)

Read WHM Setback Time Start

30103

Input

102

12:00 AM to 11:59 PM (see note)

Read WHM Setback Time
End*

30104

Input

103

12:00 AM to 11:59 PM (see note)

Read Auto Master Status

30105

Input

104

0 = NO, 1 = YES

Read Average Outlet Temp.

30106

Input

105

°F (30 to 245)

Read # Units Active

30107

Input

106

0 to 8

Read # Units Faulted

30108

Input

107

0 to 8

Read WHM Master Address

30109

Input

108

0, 10-255

Write WHM Setpoint

40200

Holding

199

°F (40 to 200)

Write WHM Setback Setpoint

40201

Holding

200

°F (40 to 200)

Write WHM Setback Time Start

40202

Holding

201

12:00 AM to 11:59 PM

Write WHM Setback Time End

40203

Holding

202

12:00 AM to 11:59 PM

WHM Heater or BST Boiler

Communication Address

3xx00

Input

(x1)

0 to 127

Unit Status

3xx01

Input

X00

Enum List (0 to 5)

0 = Disabled

1 = Standby

2 = Manual Operation

3 = Remote Operation

4 = Auto Operation

5 = Fault

Fault Code

3xx02

Input

X01

Fault codes 0-74 matching the C-
More fault codes.

Outlet Temperature

3xx03

Input

X02

°F (30 to 245)

FFWD Temperature

3xx04

Input

X03

°F (30 to 245)

Inlet Temperature

3xx05

Input

X04

°F (30 to 245)

Exhaust Temperature

3xx06

Input

X05

°F (50 to 550)

Inlet Air Temperature

3xx07

Input

X06

°F (-70 to 245)

Flame Strength

3xx08

Input

X07

% (0 to 100)

Fire Rate IN

3xx09

Input

X08

% (0 to 100)

Fire Rate OUT

3xx10

Input

X09

% (0 to 100)

Unit Type

3xx11

Input

X10

Enum List (0 to 5 or 8) (see note)

Unit Size

3xx12

Input

X11

Enum List (0 to 21) (see note)

Valve State

3xx13

Input

X12

0 = Closed , 1 = Open