Appendix a: reference, Appendix a.1: specifications, Appendix a.2: compliance with ul regulations – AERCO ProtoNode Gateway Rev 3 (with external LEDs) User Manual

Page 47: Aerco protonode gateway

Advertising
background image

AERCO ProtoNode Gateway

User Manual

OMM-0080_0H

AERCO International, Inc. • 100 Oritani Dr. • Blauvelt, NY 10913

Page 47 of 126

GF-129

Ph.: 800-526-0288

11/06/2014

Appendix A:

REFERENCE

Appendix A.1: Specifications

Appendix A.1: Specifications

ProtoNode RER

ProtoNode LER

Electrical
Connections

One 6-pin Phoenix connector, one RS-485
+/- ground port, power +/- frame ground
port.
One 3-pin RS-485 Phoenix connector, one
RS-485 +/- ground port.
One Ethernet-10/100 Ethernet port.

One 6-pin Phoenix connector, one RS-485
+/- ground port, power +/- frame ground
port.
One Ethernet 10/100 BaseT port.
One FTT-10 LonWorks port.

Approvals:

CE (EN55022;EN55024; EN60950), UL916, FCC Class A Part 15, DNP3 Conformance Tested,
OPC Self-tested for Compliance, RoHS Compliant, CSA 205 Approved
BTL Marked

LonMark Certified

Power

Requirements

Multi-mode power adapter: 9-30 VDC, 12-24 VAC

Physical

Dimensions

11.5 cm L x 8.3 cm W x 4.1 cm H (4.5 x 3.2 x 1.6 in.)

Weight:

0.2 kg (0.4 lbs)

Operating

Temperature:

-40°C to 75°C (-40°F to167°F)

Surge

Suppression

EN61000-4-2 ESD EN61000-4-3 EMC EN61000-4-4 EFT

Humidity:

5 - 90% RH (non-condensing)

(Specifications subject to change without notice)

Appendix A.2: Compliance with UL Regulations

For UL compliance, the following instructions must be met when operating the ProtoNode.

• The units shall be powered by listed LPS or Class 2 power supply suited to the expected operating

temperature range.

• The interconnecting power connector and power cable shall:

o

Comply with local electrical code.

o

Be suited to the expected operating temperature range.

o

Meet the current and voltage rating for the ProtoNode/Net

• Furthermore, the interconnecting power cable shall:

o

not exceed 3.05m (118.3”) in length.

o

Be constructed of materials rated VW-1 or FT-1 or better.

• If the unit is to be installed in an operating environment with a temperature above 65 °C, it should

be installed in a Restricted Access Area requiring a key or a special tool to gain access

• This device must not be connected to a LAN segment with outdoor wiring.

Advertising