Table H-2. BMS II Standard Holding Register Address Mapping

Modbus Data

Address (Hex)

Menu Item

Units and Range

Default/Comments

0x0034

Offset On Time
Day 1 – Hours

00 to 23 Hours

Default = 0

0x0035

Offset On Time
Day 2 – Hours

00 to 23 Hours

Default = 0

0x0036

Offset On Time
Day 3 – Hours

00 to 23 Hours

Default = 0

0x0037

Offset On Time
Day 4 – Hours

00 to 23 Hours

Default = 0

0x0038

Offset On Time
Day 5 – Hours

00 to 23 Hours

Default = 0

0x0039

Offset On Time
Day 6 – Hours

00 to 23 Hours

Default = 0

0x003A

Offset On Time
Day 7 – Hours

00 to 23 Hours

Default = 0

0x003B

Offset Enable

0 or 1
0 = Disabled
1 = Enabled

Default = 0
(Disabled)

0x003C

Header Temp Offset -10 to 10°F

Default = 0°F

0x003D

System Start
Interlock

1, 2 or 3
1 = Intlk1 Opens Start Relay
2 = Intlk2 Opens Start Relay
3 = Either Intlk Opens Start
Relay

Default = 1
(Intlk 1)

0x003E Thru

0x0045

(Reserved)

0x0046

Offset Off Time
Sun. – Minutes

0 to 59 Minutes

Default = 0

0x0047

Offset Off Time
Mon. – Minutes

0 to 59 Minutes

Default = 0

0x0048

Offset Off Time
Tue.– Minutes

0 to 59 Minutes

Default = 0

0x0049

Offset Off Time
Wed.– Minutes

0 to 59 Minutes

Default = 0

0x004A

Offset Off Time
Thu – Minutes

0 to 59 Minutes

Default = 0

0x004B

Offset Off Time
Fri. – Minutes

0 to 59 Minutes

Default = 0