Appendix a, Bms ii menus – AERCO BMS II BOILER User Manual

Page 69

Advertising
background image

APPENDIX A

A-3

APPENDIX A

_____________________________

BMS II MENUS

- Continued

AVAILABLE CHOICES OR LIMITS

MENU LEVEL & OPTION

MINIMUM

MAXIMUM

DEFAULT

FIELD ADJUST MENU – Cont.

OFFSET ENABLE

OFF,

ON

OFF

SUN
OFFS TEMP

-50.0°F

50.0°F

00.0

SUN ON HOUR

00

23

00

SUN ON MINUTE

00

59

00

SUN OFF HOUR

00

23

00

SUN OFF MINUTE

00

59

00

Etc., Up To:

SAT OFF MINUTE

00

59

00

CONFIGURATION MENU

BOILER OP MODE

SEQUENTIAL MODE,

PARALLEL MODE

SEQUENTIAL

MODE

SYS INTLK CONFIG

START ENABLED,

ALWAYS ENABLED

START ENABLED

BLR START LEVEL

001%

100%

020%

BLR STOP LEVEL

001%

040%

016%

MAX POWER INPUT

050%

100%

100%

FAIL SAFE MODE

SHUTDOWN,

CONSTANT SETPOINT

SHUTDOWN

TUNING MENU

PROPORTIONAL BND

005°F

120°F

070°F

INTEGRAL GAIN

0.00 REP/MIN

9.99 REP/MIN

0.15 REP/MIN

DERIVATIVE GAIN

-2.00 MIN.

2.00 MIN.

0.15 MIN.

HDR TEMP DEADBND

001°F

015°F

005°F

Advertising