Appendix h – AERCO BMS II BOILER User Manual

Page 94

Advertising
background image

APPENDIX H

H-2

H

-1

BMS

II

S

TANDARD

I

NPUT

R

EGISTER

A

SSIGNMENMTS

The Read Only Input Register assignments for the BMS II are listed in Table H-1 which follows:

Table H-1. BMS II Standard Input Register Address Mapping

Modbus Data

Address (Hex)

Menu Item

Units and Range

Default/Comments

0x0000

(Reserved)

0x0001

Header Temperature

40 to 220°F

0x0002

Outside Air Temperature

-60 to 120°F

0x0003

Indoor Air/Return
Temperature

40 to 220°F

0x0004

Fire Rate Out

0 to 100%
(out to boilers)

0x0005

Header Set Temperature

40 to 220°F

0x0006

Network Address

128 to 247

Default = 128

0x0007

Total Boilers Fired

0 to 32 (for BMS II)

0x0008

Total Boilers On Line

0 to 32

0x0009

(Reserved)

0x000A

Fault/Message Code

0 to 65535
Bit:
0 = Outside Air Sensor
1 = Header Sensor Error
2 = Interlock 1 Error
3 = Interlock 2 Error
4 = Indoor Air Sensor Error/
Return Sensor Error
5 = 4-20mA Input Error

0x000B

thru

0x000F

(Reserved)

0x0010

Lead Boiler Number

1 to 32