Aerco, Appendix g, Legend – AERCO BMK 3.0 LN Natural Gas July 2011 User Manual

Page 107

Advertising
background image

APPENDIX G

G-1

AIR

SEPARATOR

AUTOMATIC

AIR VENT

LINE

SIZE

BYPASS

BACKFLOW PREVENTER

DIAPHRAGM TYPE

EXPANSION TANK

WATER

SUPPLY

PRESSURE

REDUCING

FILL VALVE

CHECK

VALVE

(TYP.)

HEATING

SYSTEM

SUPPLY

SYSTEM

PUMP

P&T

RELIEF

VALVE (TYP.)

HEATING

SYSTEM

RETURN

AT MAXIMUM BTU/HR INPUT,

MAINTAIN MINIMUM NATURAL GAS PRESSURE AT

3.5" W.C. (FM GAS TRAIN)/4.0" W.C. (IRI GAS TRAIN)

MAX GAS PRESSURE = 2.0 PSIG.

(SEE NOTE 6)

* 2" MANUAL

SHUTOFF

VALVE

GAS SUPPLY

TEMPERATURE GAUGE

P&T

PRESSURE &

BALANCING VALVE

ISOLATION VALVE

UNION

Y STRAINER

LEGEND

AERCO

SD

MC

BENCHMARK 3 MIL. BTU LOW NOx

SINGLE UNIT INSTALLATION

SCALE

DWN.BY

APPD.

SD-A-681

INTERNATIONAL, INC.

NORTHVALE, NJ 07647

061506

DATE

DATE

GAS FIRED BOILER

REV.

C

DRIP TRAP

* CONDENSATE DRAIN TRAP

1-1/2" NPT

DRAIN CONN.

DOWNSTREAM OF THE 2" MANUAL SHUTOFF VALVE TO BRING THE GAS PRESSURE DOWN TO 2.0 PSIG.

6) WHEN AVAILABLE GAS PRESSURE IS GREATER THAN 2.0 PSIG, A LOCK-UP STYLE REGULATOR MUST BE INSTALLED

FITTINGS TO PREVENT INTERFERENCE WITH REMOVAL OF BOILER PANELS AND COVERS. ALL PIPING AND

FREELY, BY GRAVITY, TO A CONVENIENT FLOOR DRAIN. RELIEF VALVE SHOULD BE PIPED VERTICALLY TO A

1) FOR ACTUAL SIZES AND LOCATIONS OF PIPING AND OTHER CONNECTIONS TO THE BOILER, SEE DIMENSIONAL DRAWING (AP-A-802).

ELECTRIC CONNECTIONS (SERVICE SWITCHES, CONDUIT BOXES) SHOULD LIKEWISE

4) LOCATE WATER INLET AND OUTLET FITTINGS (i.e. UNIONS, ELBOWS, ETC.) A MINIMUM OF 6'' FROM BOILER

2) SHELL DRAIN VALVE AND CONDENSATE DRAIN TRAP SHOULD BE ARRANGED TO PERMIT THE FLUIDS TO DRAIN

5) THIS IS A TYPICAL INSTALLATION DRAWING. LOCAL CODES AND AUTHORITIES SHOULD BE CONSULTED.

BE 6'' AWAY FROM SIDE PANELS.

3) ALL (*) ITEMS ARE INCLUDED SEPARATELY IN SHIPMENT FROM FACTORY.

HEIGHT 18'' ABOVE FLOOR.

NOTES:

7) EACH CONDENSATE PORT CAN BE PIPED INDIVIDUALLY TO MAIN DRAIN.

(SEE NOTE 7)

DRIP TRAP

GAS SUPPLY

* 2" MANUAL

SHUTOFF

VALVE

Diagram 1

8) A GAS REGULATOR IS MANDATORY FOR THE STATE OF MASSACHUSETTS, REGARDLESS OF SUPPLY PRESSURE,

SEE DIAGRAM 1

MAINTAIN A REGULATED

3.5" W.C. (NAT. GAS, FM/

4.0" W.C. (NAT. GAS, IRI/GAS

PRESSURE AT MAX BTU/HR INPUT

(TO BOILER)

(SEE NOTE 8)