Aerco, Appendix g, Legend – AERCO BMK 3.0 LN Natural Gas July 2011 User Manual

Page 108

Advertising
background image

APPENDIX G

G-2

NORTHVALE, NJ 07647

INTERNATIONAL, INC.

APPD.

DWN.BY

SCALE

DATE

MC

DATE

SD

061506

AERCO

SD-A-682

C

REV.

BENCHMARK 3 MIL. BTU LOW NOx

GAS FIRED BOILER

MULTIPLE UNIT INSTALLATION

5) THIS IS A TYPICAL INSTALLATION DRAWING. LOCAL CODES AND AUTHORITIES SHOULD BE CONSULTED.

2) SHELL DRAIN VALVE AND CONDENSATE DRAIN TRAP SHOULD BE ARRANGED TO PERMIT THE FLUIDS TO DRAIN

4) LOCATE WATER INLET AND OUTLET FITTINGS (i.e. UNIONS, ELBOWS, ETC.) A MINIMUM OF 6'' FROM BOILER

ELECTRIC CONNECTIONS (SERVICE SWITCHES, CONDUIT BOXES) SHOULD LIKEWISE

1) FOR ACTUAL SIZES AND LOCATIONS OF PIPING AND OTHER CONNECTIONS TO THE BOILER, SEE DIMENSIONAL DRAWING (AP-A-802).

FREELY, BY GRAVITY, TO A CONVENIENT FLOOR DRAIN. RELIEF VALVE SHOULD BE PIPED VERTICALLY TO A

FITTINGS TO PREVENT INTERFERENCE WITH REMOVAL OF BOILER PANELS AND COVERS. ALL PIPING AND

6) WHEN AVAILABLE GAS PRESSURE IS GREATER THAN 2.0 PSIG, A LOCK-UP STYLE REGULATOR MUST BE INSTALLED

DOWNSTREAM OF THE 2" MANUAL SHUTOFF VALVE TO BRING THE GAS PRESSURE DOWN TO 2.0 PSIG.

P&T

AUTOMATIC

AIR VENT

AIR

SEPARATOR

1-1/2" NPT

DRAIN CONN.

HEIGHT 18'' ABOVE FLOOR.

3) ALL (*) ITEMS ARE INCLUDED SEPARATELY IN SHIPMENT FROM FACTORY.

BE 6'' AWAY FROM SIDE PANELS.

NOTES:

* CONDENSATE DRAIN TRAP

PRESSURE

REDUCING

FILL VALVE

DIAPHRAGM TYPE

EXPANSION TANK

BACKFLOW PREVENTER

LINE

SIZE

BYPASS

HEATING

SYSTEM

SUPPLY

SUPPLY

WATER

SYSTEM

PUMP

CHECK

VALVE

(TYP.)

HEATING

SYSTEM

RETURN

* 2" MANUAL

SHUTOFF

VALVE

RELIEF

VALVE (TYP.)

ISOLATION VALVE

BALANCING VALVE

TEMPERATURE GAUGE

LEGEND

Y STRAINER

UNION

PRESSURE &

P&T

DRIP TRAP

GAS SUPPLY

P&T

7) EACH CONDENSATE PORT CAN BE PIPED INDIVIDUALLY TO MAIN DRAIN.

(SEE NOTE 7)

* 2" MANUAL

SHUTOFF

VALVE

(TO BOILER)

Diagram 1

GAS SUPPLY

(SEE NOTE 8)

MAINTAIN A REGULATED

4" W.C. GAS PRESSURE

AT MAX BTU/HR INPUT

DRIP TRAP

8) A GAS REGULATOR IS MANDATORY FOR THE STATE OF MASSACHUSETTS, REGARDLESS OF SUPPLY PRESSURE.

SEE DIAGRAM 1

AT MAXIMUM BTU/HR INPUT,

MAINTAIN MINIMUM NATURAL GAS

PRESSURE AT 3.5" W.C. (FM GAS

TRAIN)/4.0" W.C. (IRI GAS TRAIN)

MAX GAS PRESSURE = 2.0 PSIG.

(SEE NOTE 6)