INITIAL START-UP

4-5

37. Press the

▼ arrow key until

CAL Voltage

40% is displayed.

38. Press the

CHANGE key. CAL Voltage 40%

will begin to flash.

39. The oxygen level at the 40% valve position

should be as shown below. Also, ensure that

the carbon monoxide (CO) and nitrogen

oxide (NOx) readings do not exceed the

values shown.

Combustion Oxygen Level at

40% Valve Position

Oxygen %

± 0.2

Carbon

Monoxide

NOx

7.8 %

<50 ppm

<20 ppm

40. If the oxygen level is not within the specified

range, adjust the level using the ▲ and ▼

arrow keys. This will adjust the output

voltage to the blower motor as indicated on

the display. Pressing the ▲ arrow key

increases the oxygen level and pressing the

▼ arro

w key decreases the oxygen level.

41. Once the oxygen level is within the specified

range at 40%, press the

ENTER key to store

the selected blower output voltage for the

40% valve position.

42. Press the ▲ arrow key until SET Valve

Position appears on the C-MORE display.

43. Press the

CHANGE key. SET Valve Position

will begin to flash.

44. Press the ▼ arrow key until the SET Valve

Position reads 30%, then press the

ENTER

key.

45. Press the

▼ arrow key until

CAL Voltage

30% is displayed.

46. Press the

CHANGE key. CAL Voltage 30%

will begin to flash.

47. The oxygen level at the 30% Valve Position

should be as shown below. Also, ensure that

the carbon monoxide (CO) and nitrogen

oxide (NOx) readings do not exceed the

values shown.

Combustion Oxygen Level at

30% Valve Position

Oxygen %

± 0.2

Carbon

Monoxide

NOx

8.0 %

<50 ppm

<20 ppm

48. If the oxygen level is not within the specified

range, adjust the level using the ▲ and ▼

arrow keys. This will adjust the output

voltage to the blower motor as indicated on

the display. Pressing the ▲ arrow key

increases the oxygen level and pressing the

▼ arro

w key decreases the oxygen level.

49. Once the oxygen level is within the specified

range at 30%, press the

ENTER key to store

the selected blower output voltage for the

30% valve position.

50. Press the ▲ arrow key until SET Valve

Position appears on the C-MORE display.

51. Press the

CHANGE key. SET Valve Position

will begin to flash.

52. Press the ▼ arrow key until the SET Valve

Position reads 14%, then press the

ENTER

key.

53. Press the

▼ arrow key until

CAL Voltage

14% is displayed.

54. Press the

CHANGE key. CAL Voltage 14%

will begin to flash.

55. The oxygen level at the 14% Valve Position

should be as shown below. Also, ensure that

the carbon monoxide (CO) and nitrogen

oxide (NOx) readings do not exceed the

values shown.

Combustion Oxygen Level at

14% Valve Position

Oxygen %

± 0.2

Carbon

Monoxide

NOx

8.5 %

<50 ppm

<30 ppm

56. If the oxygen level is not within the specified

range, adjust the level using the ▲ and ▼

arrow keys. This will adjust the output

voltage to the blower motor as indicated on

the display. Pressing the ▲ arrow key

increases the oxygen level and pressing the

▼ arro

w key decreases the oxygen level.

57. Once the oxygen level is within the specified

range at 14%, press the

ENTER key to store

the selected blower output voltage for 14%

Valve Position.

IMPORTANT

Repeat steps 18 through 57 until the

blower output voltage does not require

adjustment when sequencing from 70% to

14%.

58. This completes the natural gas combustion

calibration procedure.