Installation – AERCO BMK 3.0 LN Nat. Gas Jan 2011 User Manual

Page 17

Advertising
background image

INSTALLATION

2-5

CONDENSATE

TRAP

CONNECTING

MANIFOLD

DRAIN

PIPE

3/4" NPT

NIPPLES

TO

FLOOR

DRAIN

CLAMP

1" I.D.

HOSE

ADAPTOR

Figure 2-6

Condensate Trap Installation

2.7 GAS SUPPLY PIPING

The AERCO

Benchmark 3.0

Gas Components

and S upply Des ign G uide, G F-3030 m ust be

consulted prior to designing or installing any gas

supply piping.

WARNING

NEVER US E MATCHES, CANDLES,

FLAMES O R OT HER S OURCES O F

IGNITION TO CHECK FO R G AS

LEAKS

.

CAUTION

Many soaps used f or gas pipe leak

testing are corrosive to metals. There-

fore, piping must be rinsed thoroughly

with clean water af ter leak chec ks

have been completed.

NOTE

All gas piping must be ar ranged so that it

does not i nterfere with r emoval of an y

covers, in hibit s ervice/maintenance, or

restrict ac cess bet ween the unit a nd

walls, or another unit.

A 2 inch gas inlet c onnection is l ocated o n th e

rear of the unit as shown in Figure 2-4.

Prior to i nstallation, al l p ipes s hould be d e-

burred and internally cleared of any scale, metal

chips or oth er f oreign particles. Do Not install

any f lexible c onnectors or unap proved gas

fittings. Piping must be supported from the f loor,

ceiling or walls only and must not be s upported

by the unit.

A s uitable p iping c ompound, appr oved f or us e

with natur al gas , should b e used. An y excess

must be wipe d of f to prevent c logging of

components.

To avoid unit damage when pressure testing gas

piping, is olate the unit f rom the gas s upply

piping. At no t

ime s hould the g as pr essure

applied to th e un it ex ceed 2 ps i. Leak tes t al l

external p iping th oroughly us ing a s oap a nd

water s olution or s uitable equivalent. T he g as

piping used must meet all applicable codes.

2.7.1 Gas Supply Specification

The gas s upply input s pecifications to the unit

for Natural Gas are as follows:

The m aximum static pr essure to th e unit m ust

not exceed 2 psi. The gas supply pressure to the

unit m ust be of s ufficient c apacity to provide

3000 c fh whi le m aintaining the gas pr essure at

3.5” W.C. for FM or 4.0” for IRI gas trains.

2.7.2 Manual Gas Shutoff Valve

A manual shut-off valve must be ins talled in the

gas supply line upstream of the Boiler as shown

in Figure 2-7. Maximum allowable gas pressure

to the Boiler is 2 psi

NOTE

Paragraph 2.7. 3 applies onl y to bo lier

installations with in t he Co mmonwealth of

Massachusetts.

2.7.3 External Gas Supply Regulator

For Mas sachusetts installations, a m andatory

external gas supply regulator must be positioned

as s hown i n F igure 2- 7. T he gas s upply

regulator m ust be pr operly ve nted to out doors.

Consult th e l ocal gas uti lity f or det ailed

requirements c oncerning ve nting of the th e

supply gas regulator.

NOTE

The external regulator must be capable of

regulating 3, 00,000 BTU/HR of natur al

gas while m aintaining a g as pr essure to

the boiler of 3.5” W.C. for FM or 4.0” W.C.

for IRI gas trains.

CAUTION

A lock -up st yle r egulator M UST be

used w hen g as supply pr essure w ill

exceed 14” W.C.