INSTALLATION

2-6

NATURAL

GAS

SUPPLY

DIRT

TRAP

2" MANUAL

SHUTOFF

VALVE

MANDATORY

REGULATOR FOR

MASSACHUSSETTS

INSTALLATIONS ONLY

Figure 2-7

Manual Gas Shut-Off Valve Location

2.7.4 IRI Gas Train Kit

The IRI gas tr ain is a n opti onal g as tr ain

configuration which is required in some areas for

code c ompliance or f or ins urance purposes.

The IRI gas train is factory pre-piped and wired.

See Appendix F, Drawing AP-A-803 for details.

2.8 AC ELECTRICAL POWER WIRING

The AERCO Be nchmark 3.0 E lectrical Po wer

Wiring Guide, GF-3060, must be consulted prior

to c onnecting a ny AC po wer wiring t o th e u nit.

External AC po wer connections are made to the

unit inside the Power Box on the f ront pa nel of

the u nit. Remove the f ront door of the unit to

access the P ower Box m ounted directly above

the Co ntrol Box . Loosen the f our Po wer B ox

cover scre ws a nd re move co ver t o a ccess t he

AC t erminal c onnections i nside the P ower Box

(Figure 2-8).

NOTE

All elec trical c onduit a nd hardware m ust

be ins talled s o that it do es not inter fere

with the removal of any unit covers, inhibit

service/maintenance, or pr event ac cess

between the unit and w alls or ano ther

unit.

UPPER RIGHT CORNER OF FRONT PANEL

TERMINAL BLOCK

Figure 2-8

AC Input Terminal Block Location

2.8.1 Electrical Power Requirements

The AERCO Be nchmark 3 .0 Bo iler is ava ilable

in two different AC power configurations:

208 VAC/3-Phase/60 @20 amps

460 VAC/3-Phase/60 Hz @ 15 amps

Each of the power configurations utilize a Power

Box with a t erminal b lock that m atches the

configuration ordered. The two different terminal

block configurations are shown in Figure 2-9. A

wiring d iagram s howing t he r equired AC po wer

connections is provided on the front cover of the

Power Box.

Each B enchmark 3.0 Boil er must be c onnected

to a d edicated el ectrical circuit. NO O THER

DEVICES SHO ULD B E O N THE SAM E

ELECTRICAL CIRCU IT AS T HE BENCHMARK

BOILER. A m eans f or dis connecting AC p ower

from the unit ( such as a service switch) must be

installed n ear th e un it f or normal oper ation and

maintenance. All e lectrical c onnections s hould

be m ade i n ac cordance with th e Nat ional

Electrical Code and/or with any applicable local

codes.

For elec trical p ower wiring diagr ams, s ee the

AERCO Benchmark 3.0 El ectrical Power Wiring

Guide, (GF-3060).