INSTALLATION

2-9

While it is possible to c ontrol a bo iler or boilers

using one of the previously described modes of

operation, it m ay not be the method best suited

for the appl ication. Prior to s electing o ne of

these m odes of oper ation, it is r ecommended

that y ou consult w ith y our local AER CO

representative or the f actory f or the m ode of

operation th at will work bes t with

your

application. F or more information on wiring the

4 to 20 mA / 1to 5VDC or the 0 to 20 mA / 0 to 5

VDC, see paragraph 2.9.3.

2.9.5 Combination Mode

NOTE

Only BMS M odel 16 8 c an be ut ilized f or

the Com bination Mode, n ot the B MS II

(Model 5R5-384).

With a Com bination Mode un it, f ield wiring is

between the unit’s I/O Box wiring terminals, the

CCP (Combination Control Panel), and the BMS

Model 1 68 ( Boiler Ma nagement S ystem). The

wiring m ust be ac complished us ing t wisted-

shielded pair wire from 18 to 22 A WG. Polarity

must be m aintained. For further instructions and

wiring di agrams, r efer to the G

F-108 Bo iler

Management System Operations Guide and the

CCP-1 data sheet.

2.10 I/O BOX CONNECTIONS

The t ypes of input and output s ignals and

devices to be connected to the I/O Box terminals

shown in F igure 2- 11 a re des cribed i n t he

following paragraphs.

CAUTION

DO NOT make any connections to the

I/O Box t erminals labeled “

NOT

USED”. A ttempting to d o so ma y

cause equipment damage.

2.10.1 OUTDOOR SENSOR IN

An outdoor air temperature sensor (AERCO Part

No. 12 2790) will be r equired pr imarily f or th e

Indoor/Outdoor reset mode of operation. It c an

also be used with another mode if it is desired to

use th e o utdoor s ensor e nable/disable f eature.

This f eature a llows the b oiler to be enabled or

disabled based on the outdoor air temperature.

The f actory def ault f or th e out door s ensor is

DISABLED. T o enable the sensor and/or select

an enable/disable outdoor temperature, see the

Configuration menu in Chapter 3.

The outdoor sensor may be wired up to 200 feet

from the boiler. It is connected to the OUTDOOR

SENSOR IN and SENSOR COMMON terminals

in the I/O Box (see Figures 2-10 and 2-11). Wire

the s ensor us ing a t wisted s hielded pair wire

from 18 to 22 A WG. There is no po larity t o

observe when ter minating th ese wires. T he

shield is to be c onnected only t o t he terminals

labeled SHIELD in t he I/O Box. The sensor end

of the shield must be left free and ungrounded.

When mounting th e s ensor, it m ust be loc ated

on t he N orth s ide of th e bu ilding where an

average outs ide air tem perature is ex pected.

The sensor must be shielded from direct sunlight

as wel l as impingement b y the e lements. If a

shield is us ed, it m ust allo w f or f ree air

circulation.

2.10.2 AIR SENSOR IN

The AIR S ENSOR IN is c onnected t o the AUX

SENSOR IN and SENSOR COMMON terminals

on the I /O boar d. T he AI R SEN SOR m easures

the tem perature of the air inp ut to t he Air/Fuel

Valve. T his te mperature r eading is one of the

components us ed t o c alculate t he r otational

speed of the bl ower us ed in the c ombustion

Calibration process (Chapter 4).

The AUX SENSOR IN terminals can be used to

add a n ad ditional temperature s ensor f or

monitoring pur poses. T his in put is always

enabled a nd is a view-only input th at c an be

seen i n th e O perating M enu. T he s ensor m ust

be wired to the AUX SENSOR IN and SENSOR

COMMON t erminals a nd m ust be s imilar to

AERCO BALCO wire sensor Part No. 12449. A

resistance c hart f or this s ensor is pr ovided in

Appendix C.

2.10.3 ANALOG IN

The ANALO G IN + and – ter minals ar e us ed

when an ex ternal s ignal i s us ed t o dr ive t he

firing r ate ( Direct Dr ive Mode) or c hange th e

setpoint (Remote Setpoint Mode) of the Boiler.

Either a 4 to 20 mA /1 to 5 VDC or a 0 to 20 mA

/ 0 to 5 VDC s ignal m ay be us ed to vary t he

setpoint or firing rate. The factory default setting

is for 4 to 20 mA / 1 to 5 V DC, however this may

be changed to 0 to 20 mA / 0 to 5 VDC using the

Configuration Me nu des cribed i n Cha pter 3. If

voltage r ather t han c urrent is s elected as t he

drive s ignal, a DI P s witch must be s et on t he

PMC Board l ocated i nside th e Co ntrol B ox.

Contact the A ERCO f actory f or inf ormation o n

setting DIP switches.

All of the s upplied s ignals must be floating

(ungrounded) signals. Connections between the

signal s ource and the B oiler’s I/O Box must be

made using twisted shielded pair wire from 18 to