1 fault log, 2 operation time log – AERCO BMK 6000 User Manual

Page 133

Advertising
background image

Benchmark 6000 Boiler Installation, Operation & Maintenance Manual

CHAPTER 9 – RS-232 COMMUNICATION

OMM-0086_0D

AERCO International, Inc. • 100 Oritani Dr. • Blauvelt, NY 10913

Page 133 of 210

GF-133

Ph.: 800-526-0288

03/20/14

9.4.1 Fault Log

The C-More Control Panel logs the last 20 faults (0 – 19) starting with the most recent (#0).
They can be viewed in the front panel display or via the RS-232 port. The Fault Log cannot be
cleared. If the Fault Log already contains 10 faults, the earliest fault is overwritten when a new
fault occurs. A sample Fault Log display is shown in Table 9-1.

Table 9-1: Sample Fault Log Display

No.

Fault Message

Cycle Date

Time

0

Direct Drive Signal Fault

609 1/10/02

8:42am

1

Low Gas Pressure

366 7/04/01

5:29pm

2

Loss of Power

0 1/01/01

11:50am

NOTE

The Operation Time (T) Log can store thousands of records.
Therefore, to view the most recently logged record, enter “T”
followed by 0 (zero) and press Enter (i.e. T0 <Enter>). To view
earlier records in reverse chronological order, enter T and press
Enter. To go back 200 or 1000 records, enter T200 or T1000, etc.
and press Enter.

9.4.2 Operation Time Log

The Operation Time Log consists of a string of ASCII records stored in non-volatile memory
within the C-More Control Panel. Events such as power-up, ignition and turn-off are time
stamped. Data logged while the unit is running are run-length encoded. Data is logged or the
run-length incremented every 30 seconds. For a new run record to be logged, the fire rate or
flame strength must change by more than 5%, or the run mode must change. At steady-state,
the run-length is allowed to reach a maximum of 30 minutes before the record is logged. This
means that no more than 30 minutes of data can be lost if the unit loses power. Table 9-2
shows a sample Operation Time Log for a boiler:

The Operation Time Log can only be accessed through the RS-232 interface using a laptop or
other terminal device. Ten operation time records are displayed for each T command entry. The
operation time log can be cleared ONLY by factory authorized personnel using the Clear Log
option in the Factory menu.

Table 9-2: Sample Operation Time Log Display

Status

Fire Rate

Flame

Run Length

Date

Time

Off, Direct Drive

0

0

8

1/15/02

2:35pm

Run, Direct Drive

38

100

34

1/15/02

2:27pm

Run, Direct Drive

31

100

30

1/15/02

1:53am

Run, Direct Drive

35

100

2

1/15/02

1:23pm

Run, Direct Drive

29

100

0

1/15/02

1:21pm

Ignition

0

0

0

1/15/02

1:20pm

Off, Switch

0

0

35

1/15/02

12:30pm

Run, Manual

40

100

0

1/15/02

11:55am

Ignition

0

0

0

1/15/02

11:55am

Power-up

0

0

0

1/15/02

11:50am

Advertising