Benchmark 6000 Boiler Installation, Operation & Maintenance Manual

CHAPTER 3 – OPERATION

OMM-0086_0D

AERCO International, Inc. • 100 Oritani Dr. • Blauvelt, NY 10913

Page 51 of 210

GF-133

Ph.: 800-526-0288

03/20/14

Figure 3-3: SSOV Location

3.

With all required safety device switches closed, a purge cycle will be initiated and the
following events will occur:

a) The Blower relay energizes and turns on the blower.

b) The Air/Fuel Valve rotates to the full-open purge position and closes purge position

switch. The dial on the Air/Fuel Valve will read 100 (Figure 3-4) to indicate that it is
full-open (100%).

c) The VALVE POSITION bargraph will show 100%.


Figure 3-4: Air/Fuel Valve In Purge Position

STEPPER

MOTOR

TO BLOWER

100

AIR IN

DOWNSTREAM
SSOV WITH
POC SWITCH

TO AIR/FUEL

VALVE

GAS INLET

MANUAL SHUT-OFF VALVE

UPSTREAM
SSOV WITH POC &
AUX SWITCH