Benchmark 6000 Boiler Installation, Operation & Maintenance Manual

APPENDIX J – RECOMMENDED PERIODIC TESTING

OMM-0086_0D

AERCO International, Inc. • 100 Oritani Dr. • Blauvelt, NY 10913

Page 197 of 210

GF-133

Ph.: 800-526-0288

03/20/14

APPENDIX J: RECOMMENDED PERIODIC TESTING

WARNING

PERIODIC TESTING OF ALL BOILER CONTROLS AND SAFETY
DEVICES IS REQUIRED TO DETERMINE THAT THEY ARE OPERATING
AS DESIGNED. PRECAUTIONS SHALL BE TAKEN WHILE TESTS ARE
BEING PERFORMED TO PROTECT AGAINST BODILY INJURY AND
PROPERTY DAMAGE. THE OWNER OR USER OF AN AUTOMATIC
BOILER SYSTEM SHOULD SET UP A FORMAL SYSTEM OF PERIODIC
PREVENTIVE MAINTENANCE AND TESTING. TESTS SHOULD BE
CONDUCTED ON A REGULAR BASIS AND THE RESULTS RECORDED
IN A LOG-BOOK.

Item

Frequency

Accomplished

By

Remarks

Refer to indicated sections of this manual for detailed procedures

Gauges, monitors and
indicators

Daily

Operator

Visual inspection and record readings
in operator log

Instrument and
equipment settings

Daily

Operator

Visual check against factory
recommended specifications

Weekly

Operator

Verify factory settings

Firing Rate Control

Semi-

Annually

Service

Technician

Verify factory settings

Annually

Service

Technician

Check with combustion calibration test
equipment. See section 7.5 and
Chapter 4.

Flue, vent, stack or
intake air duct

Monthly

Operator

Visually inspection condition and
check for obstructions

Pilot Burner

Weekly

Operator

See section 7.2

Air/Fuel Valve position

Weekly

Operator

Check position indicator dial (section
3.11)

SSOV Leakage test

Annually

Service

Technician

Check for leakage in accordance with
the SSOV manufacturer’s (Siemens)
recommendations.

Flame failure

Weekly

Operator

Close manual gas shutoff valve and
check safety shutdown. See section 6.7

Flame signal strength

Weekly

Operator

Check flame strength using the Control
Panel Operating Menu. See section
3.4.

Low water level cut off
and alarm

Weekly

Operator

See section 6.4

Slow drain test

Semi-

Annually

Operator

Perform a slow drain test in accordance
with ASME Boiler and Pressure Vessel
Code,
Section IV.