Benchmark 750/1000 Boiler Installation, Operation & Maintenance Manual

CHAPTER 7 – MAINTENANCE

OMM-0082_0J

AERCO International, Inc. • 100 Oritani Dr. • Blauvelt, NY 10913

Page 89 of 192

GF-130

Ph.: 800-526-0288

05/21/2014

CHAPTER 7. MAINTENANCE

7.1 MAINTENANCE SCHEDULE

The unit requires regular routine maintenance to keep up efficiency and reliability. For best
operation and life of the unit, the following routine maintenance procedures should be performed
in the time periods specified in Table 7-1. For a complete inspection check list see ASME CSD-
1 chart.

In order to perform the maintenance tasks specified in Table 7-1, the following maintenance kits
are available through your local AERCO Sales Representative:

• Annual Maintenance Kit, Part No. 58025-01
• 24-Month Waterside/Fireside Inspection Kit, Part No. 58025-08 (See NOTE below)

NOTE

The 24-Month Waterside/Fireside Inspection Kit also includes the items
contained in the Annual Maintenance Kit (58025-01). Therefore, only Kit
Part No. 58025-08 is required when performing the waterside/fireside
inspections. Refer to Appendix L for recommended spare.

TO AVOID PERSONAL INJURY, PRIOR TO SERVICING ENSURE THAT
THE FOLLOWING GUIDELINES ARE STRICTLY OBSERVED:

• DISCONNECT THE AC SUPPLY BY TURNING OFF THE SERVICE

SWITCH AND AC SUPPLY CIRCUIT BREAKER.

• SHUT OFF THE GAS SUPPLY AT THE MANUAL SHUT-OFF VALVE

PROVIDED WITH THE UNIT

• ALLOW THE UNIT TO COOL TO A SAFE WATER TEMPERATURE

TO PREVENT BURNING OR SCALDING

Table 7-1: Maintenance Schedule

Section

Item

6 Mos.

12 Mos.

24 Mos.

Labor

Time

7.2

Igniter-Injector Kit

(58023)

*Inspect

Inspect

Replace

15 mins.

7.3

Flame Detector Kit

(24356-1)

*Inspect

Inspect

Replace

15 mins.

7.4

Lean O

2

Sensor

(61026)

*Inspect

Inspect

15 mins.

7.5

Combustion

Calibration

*Check

Check

1 hr.

7.6

Testing of Safety

Devices

See ASME

CSD-1 Chart

45 mins.

7.7

Burner

Inspect

2 hrs.

7.8

Condensate Drain

Trap

*Inspect

Inspect, Clean

& Replace

Gaskets

Inspect, Clean

& Replace

Gaskets

30 mins.

7.9

Air Filter (59139)

Clean

Replace

15 mins.

* Only performed after initial 6 month period after initial startup.