Figure 2.8, Ac power box location, Ac power wiring diagram – AERCO KC1000 Boiler July 2011 User Manual

Page 16: Figure 2.10, Input/output (i/o) box location, Installation

Advertising
background image

INSTALLATION

2-6

be run from the knockouts in the side of the box

in such a manner that it does not interfere with

the removal of any sheet metal covers. A flexible

electrical connection may be utilized to allow the

covers to be easily removed.

POWER BOX

BLOWER

SSOV

ACTUATOR

FRAME

Figure 2.8

AC Power Box Location

NOTE:

All electrical conduit and hardware should

be installed so that it does not interfere with

the removal of any cover, inhibit service or

maintenance, or prevent access between

the unit and walls or another unit.

2.5.1 ELECTRICAL REQUIREMENTS

Electrical requirements for each unit are 120

VAC, 1 Phase, 60 Hz, 20 Amps from a

dedicated electrical circuit. No other devices

should be on the same electrical circuit as a

KC1000 unit.
A double-pole switch must be installed on the

electrical supply line in an easily accessible

location to quickly and safely disconnect

electrical service. DO NOT attach the switch to

sheet metal enclosures of the unit.
After placing the boiler in service, the ignition

safety shutoff device must be tested. If an

external electrical power source is used, the

installed boiler must be electrically bonded to

ground in accordance with the requirements of

the authority having jurisdiction. In the absence

of such requirements, the installation shall

conform to National Electrical Code (NEC),

ANSI/NFPA 70 and/or the Canadian Electrical

Code (CEC) Part I, CSA C22.1 Electrical Code.
The AC power wiring diagram is shown in Figure

2.9.

USE COPPER CONDUCTORS ONLY FOR FIELD WIRING

60 HZ

DISCONNECT POWER BEFORE SERVICING

DANGER: HIGH VOLTAGE

20 AMP

120 VAC,

NEUTRAL

GROUND

LINE

POWER BOX

AERCO INTERNATIONAL INC.

INPUT POWER

Figure 2.9

AC Power Wiring Diagram

2.6 MODE OF OPERATION and FIELD

CONTROL WIRING

The KC Boiler is available in several different

modes of operation. While each unit is factory

configured and wired for the mode specified on

the equipment order, some field wiring may be

required to complete the installation. This wiring

is typically routed to the Input/Output (I/O) Box

located on the left side of the unit beneath the

removable side panel (see Figure 2.10). Field

wiring for each particular mode of operation is

described in the following paragraphs. For

additional information concerning modes of

operations, refer to Section 5.

I/O

BOX

GAS SHUT-OFF VALVE

BLOWER

Figure 2.10

Input/Output (I/O) Box Location

Advertising