2 bcm (boiler communications module) fault codes – AERCO Modulex EXT 321 - 1123 User Manual

Page 117

Advertising
background image

MODULEX EXT 321, 481, 641, 802, 962, 1123 BOILERS

Installation, Operation & Maintenance Manual

BCM (Boiler Communications Module) Fault Codes

6.1.2

The table below lists the fault codes and troubleshooting tips associated with the BCM.

Table 6-3: BCM Fault Codes

CODE

DESCRIPTION

EFFECT

CORRECTION

RESET

E 17

Boiler pipe is frozen.
Flow sensor temp. is
36°F or less.

Ignition is
inhibited. Pump
runs for 5 min at
max speed.

Carefully
defrost boiler.

AUTOMATIC - when Flow
sensor is greater than 41°F.

E 18

Maximum Δ-
temperature protection.
Flow temperature -
Return Temperature >
Water

Δ-Temp

Protection + 50°F

All burners turned
OFF and Pump
ON at maximum
speed.

Check the
system
installation.

AUTOMATIC -

when Δ-

temperature < Water Δ-
Temp Protection.

E 19

High outlet
temperature. Flow
sensor temperature >
203°F.

All burners turned
OFF and pump
ON at maximum
speed.

Check Flow
Sensor or
system pump.

AUTOMATIC - when Flow
sensor < 176°F.

E 37

BCM: Internal fault

E 38

Settings corrupted by
electromagnetic
interference.

Ignition is
inhibited. Pump
runs for 5 min at
max speed.

Re-program
the settings.
Contact
factory.

MANUAL - push reset
switch or cycle power.

E 56

BCM: No remote
control detected

E 57

BCM: No BMM
detected

E 58

BCM: Sensor global
flow detected.

Ignition is
inhibited.

Close request
input for
manual
operation.

MANUAL - push reset
switch or cycle power.



OMM-0087_0E

AERCO International, Inc. • 100 Oritani Dr. • Blauvelt, NY 10913

Page 117 of 148

GF-143

Phone: 800-526-0288

12/01/14