MODULEX EXT 321, 481, 641, 802, 962, 1123 BOILERS

Installation, Operation & Maintenance Manual

Table 6-4: BMM Fault Codes (Continued)

CODE DESCRIPTION

EFFECT

CORRECTION

RESET

E 24

Fan speed out of
control: It
doesn't reach
pre-purge speed
within 30
seconds.

Ignition retry
after 60
second delay
and failure
remains until
we have a
successful
burner
operation.

Check fan wiring.

AUTOMATIC/MANUAL

E 26

Fan speed out of
control: It
doesn't stop
within 30
seconds after
turned OFF.

Ignition is
inhibited.

Check fan wiring.

AUTOMATIC

E 27

Air flow failure
during ignition.

Restart pre-
purge timer.
The failure
remains until
we have a
successful
burner
operation.

Check fan and wiring.
Check air proving switch
and wiring.

AUTOMATIC

E 30

Settings
corrupted.

Ignition is
inhibited.
Pump runs for
5 min at max
speed.

Re-program the settings.
Contact factory.

MANUAL - cycle the
power or send reset
message.

E 32

Line voltage too
low (<96 VAC).

Wait for
proper line
voltage (>102
VAC).

Check input voltage. Try
another BMM.

AUTOMATIC

E 40

Low water flow.
Low water flow
switch activated.

Burners
turned OFF.

Check water flow or
check switch.

AUTOMATIC


Page 120 of 148

AERCO International, Inc. • 100 Oritani Dr. • Blauvelt, NY 10913

OMM-0087_0E

12/01/14