MODULEX EXT 321, 481, 641, 802, 962, 1123 BOILERS

Installation, Operation & Maintenance Manual

3.30 Starting Up: Filling and Deaerating the Boiler

Carry out the following tasks in connection with maintenance, etc. to an already installed unit:

Shut down all programs
Close the gas shutoff valve upstream from the boiler
Shut off the power at the main power switch
Close the C/H service valves (supply and return)

Necessary Precautions for Safety

3.30.1

Observe the following rules of safety:

• All work on the unit must take place in a dry environment.
• AERCO units should never be in operation without their cover panels, except in connection with

maintenance or adjustments.

• Never allow electrical or electronic components to come into contact with water.

Supply Voltage, Gas Pressure, and Water pressure

3.30.2

The unit must be able to function during maintenance procedures or when adjustments are
performed. For this reason, the unit’s supply voltage, gas pressure and water pressure must be
maintained and available during these activities.

WARNING!

Following maintenance or other activities, always check the integrity
of all parts through which gas flows with a bubble test using soap
spray to ensure there are no gas leaks.

3.31 Filling the System

Necessary Precautions While Filling the System

3.31.1

Do not mix the C/H system’s water with anti-freeze or anti-corrosion solutions using incorrect
concentrations! Doing so can cause damage to the gaskets and might cause noise during
normal boiler operation.

WARNING!

AERCO refuses all liability for injury to persons, animals or damage
to property deriving from not having respected the above mentioned
recommendations.

Before filling the heating system, the complete system, including all zones, must be thoroughly
cleaned and flushed to remove sediment.

Flush until clean water runs free of sediment. AERCO suggests using an approved system
cleaner to flush the system, but not the boiler. Always use AERCO approved antifreezes. See
the list in section 1.9.3, Water Quality Requirements.

Never use reverse osmosis, deionized, distilled water or mineral treated water for filling the
heating system.

OMM-0087_0E