SmartPlate Installation, Operation & Maintenance Manual

APPENDIX A – MODBUS CONTROL AND COMMUNICATION

Page 98 of 138

AERCO International, Inc.

 100 Oritani Dr.  Blauvelt, NY 10913

OMM-0069_0E

PRI: 11/26/2013

Phone: 800-526-0288

SP-100

A.3 PROCESS & DIAGNOSTIC ALARMS

The Process and Diagnostic Alarms that can appear in the Temperature Controller display are
listed in the following Tables.

PROCESS ALARMs

DISPLAY MEANING

_FSL*

PV Full Scale Low Alarm.

_FSH*

PV Full Scale High Alarm.

_dEu*

PV Deviation Band Alarm

_dHi*

PV Deviation High Alarm

_dLo*

PV Deviation Low Alarm

DIAGNOSTIC ALARMs

DISPLAY MEANING

WHAT

TO

DO`

EE.Er

Electrically Erasable Memory
Error:

The value of an

operator, or configuration,
parameter has been
corrupted.

This fault will automatically take you into
Configuration level. Check all of the
configuration parameters before returning
to Operator level. Once in Operator level,
check all of the operator parameters
before resuming normal operation. If the
fault persists, or occurs frequently,
contact your supplier

S.br

Sensor Break: Input sensor is
unreliable or the input signal
is out of range.

Check that the sensor is correctly
connected

Hw.Er

Hardware Error
Indication that a module is of
the wrong type, missing, or
faulty.

Check to ensure that the correct items
are installed. See page A-4 for procedure
to clear the Hardware Error.

n o . i o

No I/O
None of the expected I/O
items are installed

This error message normally occurs
when pre-configuring a controller without
installing any of the required I/O modules.

r m t . F

Remote input failure.
The remote DC input is open
or shorted

Check for open or short circuit wiring on
the remote DC input.

L L L L

Out of range low reading

Check the value of the input

H H H H

Out of range high reading

Check the value of the input

E r r 1

Error 1: ROM self-test fail

Return Controller for repair