Appendix a – innovation menu item descriptions – AERCO Innovation (G-13-1854 and above) User Manual

Page 121

Advertising
background image

Innovation Water Heaters Installation, Operation & Maintenance Manual

APPENDIX A – INNOVATION MENU ITEM DESCRIPTIONS

OMM-0078_0J

AERCO International, Inc. • 100 Oritani Dr. • Blauvelt, NY 10913

Page 121 of

196

GF-128

Phone: 800-526-0288

PRI: 11/22/2013

APPENDIX A – INNOVATION MENU ITEM DESCRIPTIONS

MENU LEVEL & OPTION

DESCRIPTION


OPERATING MENU

Active Setpoint

This is the setpoint temperature to which the control is set
when operating in the Constant Setpoint or Remote Setpoint
Mode. When in the Constant Setpoint Mode, this value is
equal to the Internal Setpoint setting in the Configuration
Menu. When in the Remote Setpoint Mode, this value is the
setpoint equivalent to the remote analog signal supplied to
the unit

Air Temp

For monitoring purposes only

Outdoor Temp

Displayed only if outdoor sensor is installed and enabled.

Valve Position In

Desired input valve position. This would normally be the
same as the valve position shown on the bargraph when the
heater is operating.

Flame Strength

Displays flame strength from 0% to 100%.

Run Cycles

Displays the total number of run cycles from 0 to 999,999.

Run Hours

Displays total run time of unit in hours from 0 to 9,999,999.

Fault Log

Displays information on the last 20 faults (0 – 19).

SETUP MENU

Password

Allows password to be entered.
Once the valid password (159) is entered, options in the
Setup, Configuration and Tuning Menus can be modified.

Language

English only

Time

Displays time from 12:00 am to 11:59 pm.

Date

Displays dates from 01/01/00 to 12/31/99

Unit of Temp

Permits selection of temperature displays in degrees
Fahrenheit (°F) or degrees Celsius (°C). (Default = °F)

Comm Address

For RS-485 communications (0 to 127). Default address is 0.
RS-232 should have its own (programmable) password.

Baud Rate

Allows communications Baud Rate to be set (2400 to 19.2K).
(Default = 9600)

Software Version

Identifies the current software version of the control box (Ver
0.0 to Ver 9.9).