Innovation Water Heaters Installation, Operation & Maintenance Manual

CHAPTER 3 – OPERATION

OMM-0078_0J

AERCO International, Inc. • 100 Oritani Dr. • Blauvelt, NY 10913

Page 43 of

196

GF-128

Phone: 800-526-0288

PRI: 11/22/2013

Table 3-4. Configuration Menu - Continued

Available Choices or Limits

Menu Item Display

Minimum

Maximum

Default

Remote Signal
(If Mode = Remote
Setpoint, Direct Drive
or Combination)

4 – 20 mA/1 – 5V

0 -20 mA/0 – 5V

PWM Input (Legacy BMS),

Network

4 – 20 mA,

1-5V

Bldg Ref Temp
(If Mode = Outdoor
Reset)

40°F

230°F

70°F

Reset Ratio
(If Mode = Outdoor
Reset)

0.1

9.9

1.2

Outdoor Sensor

Enabled or Disabled

Disabled

System Start Tmp
(If Outdoor Sensor =
Enabled)

30°F

100°F

60°F

Setpt Lo Limit

40°F

Setpt Hi Limit

60°F

Setpt Hi Limit

Setpt Lo Limit

220°F

140°F

Temp Hi Limit

40°F

240°F

160°F

Max Valve Position

40%

100%

100%

Pump Delay Timer

0 min.

30 min.

0 min.

Aux Start On Dly

0 sec.

120 sec.

0 sec.

Failsafe Mode

Shutdown or Constant Setpt

Shutdown

Low Fire Timer

2 sec.

600 sec.

2 sec.

Setpt Limiting

Enabled or Disabled

Disabled

Setpt Limit Band

0°F

10°F

0

Network Timeout

5 Sec

999 Sec

30 Sec

HI DB Setpt EN

0%

100%

30%

Demand Offsert

0

25

0

Deadband High

0

25

0

Deadband Low

0

25

0

DO NOT CHANGE the Analog Output Menu Item from its Default
setting (Valve Position 0-10V).

3.7 WATER HEATER MANAGEMENT (WHM) MENU

The WHM Menu in each C-More can only be viewed when the Unit Type option in the
Configuration Menu is set to Innovation WH. Most of the options in this menu are preset at the
factory and cannot be altered by the user. Therefore, the WHM Menu contains only eight (8)
user-selectable menu options. These menu options are listed in Table 3-5. Descriptions for each
of these menu items are included in Appendix A.

*