7 system recirculation loop – AERCO Innovation (G-14-2265 and above) User Manual

Page 22

Advertising
background image

Innovation Water Heaters Installation, Operation & Maintenance Manual

CHAPTER 2 – INSTALLATION

Page 22 of

206

AERCO International, Inc. • 100 Oritani Dr. • Blauvelt, NY 10913

OMM-0078_0L

PRI: 11/25/2014

Phone: 800-526-0288

GF-128


Figure 2-4. Test Hose Bib Location

2.7 SYSTEM RECIRCULATION LOOP

The System Recirculation Loop Assembly is located inside the unit enclosure at the rear of the
unit. In order to access this assembly, the right rear middle panel must be removed. Refer to
Figure 2-5. This assembly contains a recirculation pump that connects the upper hot water
outlet to the lower cold water inlet of the unit’s heat exchanger. The purpose of this loop is to
provide feed-forward (FFWD) temperature control by mixing a portion of the hot water outlet
with the cold water inlet of the unit. Temperature sensors located in the hot water outlet and cold
water inlet provide temperature data to the C-More Control System. The Control System utilizes
this data to modulate the fire rate (Air/Fuel Valve position) to precisely maintain the hot water
outlet temperature at the selected setpoint temperature.

TO DRAIN

TEST
HOSE BIB

HOT

WATER

OUT

HOSE
CONNECTION

Advertising