Innovation Water Heaters Installation, Operation & Maintenance Manual

CHAPTER 2 – INSTALLATION

OMM-0078_0L

AERCO International, Inc. • 100 Oritani Dr. • Blauvelt, NY 10913

Page 25 of

206

GF-128

Phone: 800-526-0288

PRI: 11/25/2014

If a floor drain is not available, a condensate pump can be used to remove the condensate to
drain. The maximum condensate flow rate is 10 GPH. The condensate drain trap, associated
fittings and drain line must be removable for routine maintenance.

Use PVC, stainless steel, aluminum or polypropylene for condensate drain
piping (Figure 2-7). DO NOT use carbon or copper components.

NOTE

Two different styles of condensate traps are currently in use. The functions
and connections provided are nearly identical however they look slightly
different.

LEFT SIDE VIEW

Figure 2-7. Sample Condensate Trap Installation

NOTE

As a general guideline, AERCO recommends use of its Condensate
Neutralizer Kit to raise the pH level of the condensate prior to drainage. At
a minimum, the installation must be designed in accordance with local
codes that specify acceptable pH limits. For more information, see
Technical Instruction Document TID-0029, Condensate Neutralization Kit
and TID-0074 Condensate Neutralization Tank.

CAUTION

Housekeeping pad should not extend under the condensate assembly

HOUSEKEEPING

SUPPOR

EXHAUST
MANIFOLD

CONDENSATE

TRAP

TO

FLOOR

DRAIN

3/4”

NIPPLES

1” I.D.

HOSE &

CLAMP

ADAPTER

WITH

INTERNAL