Troubleshooting – AERCO KC1000 Low NOx Water Heater July 2011 User Manual

Page 71

Advertising
background image

TROUBLESHOOTING

7-7

KC1000 WATER HEATER TROUBLESHOOTING TABLE – Continued

FAULT INDICATION

PROBABLE CAUSES

CORRECTIVE ACTION

LINE VOLTAGE

OUT OF PHASE

1. Line and Neutral

switched in AC Power

Box.

2. Incorrect power supply

transformer wiring.

1. Check hot and neutral in AC Power Box to

ensure they are not reversed

2. Check transformer wiring, in AC Power Box,

against the power box transformer wiring diagram

to ensure it is wired correctly

LOW GAS

PRESSURE

1. Incorrect supply gas

pressure.

2. Defective or incorrectly

sized Gas Supply

Regulator.

3. Defective Low

Pressure Gas Switch

1. Measure gas pressure upstream of the supply

gas regulator with the unit firing ensure it is 14”

WC or greater.

2. Measure gas pressure downstream of the supply

regulator with unit firing and adjust the gas supply

regulator to increase the outlet gas pressure; if

outlet gas pressure cannot be increased, check

the sizing of the Supply regulator.

3. Measure gas pressure at the low gas pressure

switch, if it is greater than 5” WC measure

continuity across the switch and replace if

necessary.

LOW WATER

LEVEL

1. Insufficient water level

in system

2. Defective water level

circuitry.

3. Defective water level

probe.

1. Check system for sufficient water level.
2. Test water level circuitry using the Control Box

front panel LOW WATER TEST and RESET

buttons. Replace water level circuitry if it does

not respond.

3. Check continuity of probe end to the shell,

change probe if there is no continuity.

MODBUS COMM

FAULT

1. Water Heater not

seeing information

from modbus network

1. Check network connections. If fault persists,

contact qualified Service Personnel.

PRG SWTCH CLOSED

DURING IGNITION

1. A/F Valve rotated open

to purge and did not

rotate to ignition

position

2. Defective or shorted

switch.

3. Switch wired

incorrectly.

1. Start the unit. The Air/Fuel Valve should rotate to

the purge (open) position, then back to ignition

position (towards closed) during the ignition

cycle. If the valve does not rotate back to the

ignition position, check the Air/Fuel Valve

calibration. If calibration is okay, the problem

may be in the Air/Fuel Valve or the Control Box.

Refer fault to qualified service personnel.

2. If the Air/Fuel Valve does rotate to the ignition

position, check the purge switch for continuity

between the N.O. and COM terminals. If the

switch shows continuity when not in contact with

the cam, check to ensure that the switch is wired

correctly (correct wire numbers on the normally

open terminals).

3. If switch is wired correctly, replace switch.

Advertising